Instructions, standard functions/function blocks
Hide thumbs Also See for MELSEC iQ-F FX5:

Advertisement

■Control data
Device
Item
(s1)+0
Error completion type
(s1)+1
Completion status
(s1)+2
Own station channel
(s1)+3
Target station CPU type
(s1)+4
Target network number
(s1)+5
Target station number
(s1)+6
Not used
(s1)+7
Number of resends
(s1)+8
Arrival monitoring time
(s1)+9
Read data length
(s1)+10
Not used
(s1)+11
Clock set flag
(s1)+12
Clock data
(Set only in an
abnormal state)
(s1)+13
(s1)+14
(s1)+15
(s1)+16
Error detection network
*1
number
(s1)+17
Error-detected station
*1
number
*1 If completion status ((s1)+1) is "Channel in use (dedicated instruction) (error codes: D25AH and D25BH)", data is not stored.
Description
...
b15
b8
b7
b6
0
(1)
(1) Error completion type (bit 7)
Specify whether to set data at completion with an error.
• 0: Do not set data in (s1)+11 and later at completion with an error.
• 1: Set data in (s1)+11 and later at completion with an error.
The instruction completion status is stored.
• 0: Normal
• Other than 0: Error (error code)
Specify the channel to be used by own station.
Specify the CPU type of the target station.
• 0000H: Addressed to target station CPU (control CPU)
• 03D0H: Addressed to control system CPU
• 03D1H: Addressed to standby system CPU
• 03D2H: Addressed to system A CPU
• 03D3H: Addressed to system B CPU
• 03E0H: Addressed to multiple CPU No. 1
• 03E1H: Addressed to multiple CPU No. 2
• 03E2H: Addressed to multiple CPU No. 3
• 03E3H: Addressed to multiple CPU No. 4
• 03FFH: Addressed to target station CPU (control CPU)
Specify the network number (1 to 239) of the target station.
Specify the station number of the target station.
• 125: Master station
• 126: Master operating station
• 1 to 120: Local station, intelligent device station, submaster station
■Before instruction execution
Specify the number of resends to be performed if the instruction is not completed
within the monitoring time specified by (s1)+8.
■At completion of instruction
The number of resends performed (result) is stored.
Specify the monitoring time until completion of processing. If processing is not
completed within the monitoring time, the request is resent by the number of
resends specified in (s1)+7.
• 0: 10 seconds
• 1 to 32767: 1 to 32767 seconds
Specify the number of words to be read.
• 1 to 960 (words)
(When reading data from QnACPU: 1 to 480 (words))
The validity status (valid or invalid) of the data in (s1)+12 and later is stored. Note
that the data in (s1)+12 and later is not cleared even when the instruction is
completed successfully.
• 0: Invalid
• 1: Valid
Upper 8 bits: Month (01H to 12H)
Lower 8 bits: Lower 2 digits of year (00H to 99H)
Upper 8 bits: Hour (00H to 23H)
Lower 8 bits: Day (01H to 31H)
Upper 8 bits: Second (00H to 59H)
Lower 8 bits: Minute (00H to 59H)
Upper 8 bits: Upper 2 digits of the year (00H to 99H)
Lower 8 bits: Day of the week (00H (Sun.) to 06H (Sat.))
The network number of the station in which an error was detected is stored. (No
information is stored if an error is detected in the own station.)
• 1 to 239 (Network number)
The station number of the station where an error was detected is stored. (No
information is stored if an error is detected in the own station.)
• 125: Master station
• 1 to 120: Local station, intelligent device station, submaster station
...
b0
0
12 NETWORK COMMON INSTRUCTION
12.1 Link Dedicated Instructions
Setting range
Set by
0000H
User
0080H
System
1, 2
User
0000H
User
03D0H to 03D3H
03E0H to 03E3H
03FFH
1 to 239
User
1 to 120, 125, 126
User
0 to 15
User/
system
0 to 32767
User
1 to 960
User
System
System
System
System
System
System
System
769
12