• As a reset instruction for individual devices, the RST instruction can be used for bit devices and word devices.
X1
RST
M0
RST
T0
RST
D0
(1): M0 is reset.
(2): The current value of T0 is reset.
(3): D0 is reset.
• The FMOV(P) instruction is a batch write instruction for a constant (K0 for example) that can write "0" for word devices
(including nibble specification of bit devices).
X2
FMOV
K0
D0
(1): K0 is written to D0 to D99.
Precautions
• Specify the same type of device for (d1) and (d2) so that (d1) number is less than (d2) number. If the (d1) number(d2)
number, only the device specified by (d1) is reset.
• The ZRST(P) instruction is a 16-bit instruction, but long counter (LC) and long index register (LZ) can be specified for (d1)
and (d2).
X0
ZRST
C180
ZRST
LC0
Operation error
Error code
Description
(SD0/SD8067)
2820H
The number of devices to be reset is 32768 or more when module access device has been specified for (d1) and/or (d2).
3405H
Device type specified by (d1) differs from type specified by (d2).