Common items among the FROM(P), DFROM(P), TO(P), and DTO(P) (details)
• Use the module number to specify which Intelligent function module the instruction works for. The setting range is from H1
to H10 (K1 to K16).
CPU
I/O
module
module
• A module number is automatically assigned to each intelligent function module connected to a CPU module. The module
number is assigned in the way "No. 1  No. 2  No. 3 ..." starting from the equipment nearest the CPU module.
• 16-bit RAM memories are built in an intelligent function module, and they are called buffer memories. The contents of buffer
memories vary depending on the purpose of control of each Intelligent function module, and the setting range is from K0 to
K65535.
• The number of read data is specified by (n), and the setting range is from K1 to K65535.
Specified device
D100
D101
D102
D103
D104
n = 5
• If this instruction is executed in an interrupt program with the priority 1, operation error (3580H) occurs. This instruction
operates in an interrupt program with the priority 2 or 3.
• If this instruction is executed to an FX3 intelligent function module within an interrupt program, operation error (3580H)
occurs.
8 APPLICATION INSTRUCTION
722
8.26 Module Access Instruction
Module
Module
No. 1
No. 2
Intelligent
Extension
Intelligent
function
power
function
module
supply unit
module
Specified BFM
BFM#5
#6
#7
#8
#9
Module
Module
No. 3
No. 4
Intelligent
Bus
I/O
function
conversion
module
module
module
Module
No. 5
Intelligent
function
module