Vertical WAVE IP 2500 Installation Manual page 22

Hide thumbs Also See for WAVE IP 2500:
Table of Contents

Advertisement

Wave IP 2500 Installation Guide
'PXKTQPOGPVCN 4GSWKTGOGPVU
For the Wave IP 2500 to operate properly, the environmental specifications in the following
table must be met.
+VGO
Temperature, operating
Temperature, storage
Relative humidity, operating
Relative humidity, storage
Operating altitude
Clearance for servicing
Clearance for cooling
AC power source
Heat emitted
Power consumption
Internal power supply
4GSWKTGF 6QQNU
You need the following tools to install the Wave IP 2500:

#1 and #2 Phillips screwdriver
Flat-head screwdriver
Antistatic mat to protect electronic components from static electricity damage
Antistatic wrist strap attached to a grounded, antistatic leash
For Review Only - Draft Document 09/07/07
COMPANY CONFIDENTIAL - DO NOT Distribute
8CNWG
32° to 104° F (0° to 40° C)
-4° to 140° F (-20° to 60° C)
5-80%, non condensing
Maximum 85%, non condensing
Maximum 10,000 ft (3050 m)
Minimum 24 in (61 cm) front and back
Minimum 4 in (10 cm) on all sides
15-amp circuit required
Maximum 2830 BTU/hour main chassis, 1910 BTU/hour EXU
chassis
Maximum 830W main chassis, 560W EXU chassis
Input voltage: 100-120 VAC, 50/60 Hz
Input current: maximum 9A main chassis, 6A EXU chassis