24.3.4 TN – Reset time of the process controller
The reset time specifies the I-contribution of the PID controller
(can be set with the aid of the P.TUNE function).
Factory setting: 999.9 s
Operating structure:
PID.PARAMETER
ENTER
EXIT
Figure 55:
Operating structure TN; reset time
24.3.5 TV – Hold-back time of the process controller
The hold-back time specifies the D-contribution of the PID controller
(can be set with the aid of the P.TUNE function).
Factory setting: 0.0 s
Operating structure:
PID.PARAMETER
ENTER
EXIT
Figure 56:
Operating structure TV; hold-back time
24.3.6 X0 – Operating point of the process controller
The operating point corresponds to the size of the proportional portion when control difference = 0.
Factory setting: 0.0 %
Operating structure:
PID.PARAMETER
ENTER
EXIT
Figure 57:
Operating structure X0; operating point
DBND 1.0 %
TN
999.9
INPUT
FILTER
0
DBND 1.0 %
TV
0.0
INPUT
FILTER
0
DBND 1.0 %
X0
0.0 %
INPUT
FILTER
0
Input value
Adjustment range: 0.5 ... 999.9 s
Input value
Adjustment range: 0 ... 999.9 s
Input value
Adjustment range: 0 ... 100 %