25.2.6 X .LIMIT – Limits the mechanical stroke range
This auxiliary function limits the (physical) stroke to specified % values (minimum and maximum). In doing so, the
stroke range of the limited stroke is set equal to 100 %.
If the limited stroke range is left during operation, negative POS values or POS values greater than 100 % are indicated.
Factory setting:
X.LIMIT
ENTER
EXIT
* If the submenu is left by pressing the
Figure 73:
Operating structure X.LIMIT
The changed data is saved in the memory (EEPROM) only when there is a switch to the process level,
by leaving the main menu (MAIN) using the left selection key
symbol is indicated
Limited stroke (%)
(POS)
Figure 74:
Graph - X.LIMIT
120
Min = 0 %,
Max = 100 %
Min
0 %
Max 100 %
The minimum gap between Min and Max is 50 %
ESC
key, the value remains unchanged.
on the display.
Physical stroke (%)
(POS)
english
INPUT
Enter
value
INPUT
Enter
value
*
OK
EXIT
Unlimited stroke
Limited stroke
Type 8692, 8693
Auxiliary functions
Input the initial value of the stroke
range as %.
Adjustment range:
0 – 50 % of the total stroke
Input the final value of the stroke
range as %.
Adjustment range:
50 – 100 % of the total stroke
. During the save process, the save
Set-point value [mA]
(INPUT)