Connection.diagram.profibus.dp; X2.-.M12.Socket,.5-Pole.(Bus.connection); X6.-.M12.Circular.connector,.4-Pole.(Operating.voltage) - Burkert 8692 Operating Instructions Manual

Electropneumatic positioner and process controller
Table of Contents

Advertisement

Type 8692, 8693
PROFIBUS DP
28.1
Connection diagram PROFIBUS DP
Figure 125:
Electrical connection PROFIBUS DP, Type 8692/8693
28.2
X2 - M12 socket, 5-pole (bus connection)
Pin
Configuration
1
VP+5
2
RxD/TxD-N
3
DGND
4
RxD/TxD-P
5
Schirm
Table 99:
X2 - M12 socket, 5-pole - bus connection, PROFIBUS DP
28.3
X6 - M12 circular connector, 4-pole (operating
voltage)
Pin Wire.color* Configuration
1
brown
+24 V
2
not used
3
blue
GND
4
not used
* The indicated wire colours refer to the connection cable, part no. 918038, available as an accessory.
Table 100:
X6 - M12 circular connector, 4-pole (operating voltage)
1
X2.-.M12.socket,.5-pole.
5
(inversely coded)
(PROFIBUS DP)
4
2
3
X5.-.M8.circular.connector,.4-pole..
1
3
(only.Type.8693).
Input signals
4
2
Process actual value
2
X6.-.M12.circular.connector,.4-pole.
3
1
Operating voltage
4
Earthing screw (TE)
Switch (to operate loosen the screw connection)
External.circuit./.Signal.level
Supply the terminating resistors
Received/transmitted data -N, A-line
Data transmission potential (earth to 5 V)
Received/transmitted data -P, B-line
Shielding / protective earth
On.the.device.side External.circuit./.Signal.level
1
3
24 V DC ± 10 %
max. residual ripple 10%
english
197

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

8693

Table of Contents