Type 8692, 8693
Start-Up
Operating structure:
SP-SCALE
ENTER
EXIT
Figure 50:
Operating structure SP-SCALE
Scaling.process.set-point.value.SETUP.→.SP-SCALE:
Key
Action
/
Select SP-SCALE
ENTER
Press
/
Select SPmin
INPUT
Press
/
Increase value
<–
Select decimal place
OK
Press
/
Select SPmax
INPUT
Press
/
Increase value
<–
Select decimal place
OK
Press
EXIT
Press
Table 41:
SP-SCALE; scaling process set-point value
If the submenu is left by pressing the left selection key
SPmin
INPUT
INPUT
SPmax
Description
The submenu options for scaling of the process set-point value are
displayed.
The input screen is opened.
Set scaling value (lower process set-point value).
The value is assigned to the smallest current or voltage value of the
standard signal.
Return to SP-SCALE.
The input screen is opened.
Set scaling value (upper process set-point value).
The value is assigned to the largest current or voltage value of the
standard signal.
Return to SP-SCALE.
Return to SETUP.
Input lower process set-point
value
Input upper process set-point
value
, the value remains unchanged.
ESC
English
*
OK
*
OK
95