Connection.diagram.devicenet,.Type.8692/8693; X3.-.M12.Circular.connector,.5-Pole.(Bus.connection); X6.-.M12.Circular.connector,.4-Pole.(Operating.voltage) - Burkert 8692 Operating Instructions Manual

Electropneumatic positioner and process controller
Table of Contents

Advertisement

Type 8692, 8693
DeviceNet
31.1
Connection diagram DeviceNet, Type 8692/8693
Figure 132:
Electrical connection DeviceNet, Type 8692/8693
The device is supplied by the operating voltage, galvanically isolated from the DeviceNet, not by the V+ and
V- voltage of the DeviceNet.
31.2
X3 - M12 circular connector, 5-pole (bus
connection)
Pin
Signal
1
Shielding
2
V+
3
V–
4
CAN H
5
CAN L
Table 109:
X3 - M12 circular connector, 5 pole (bus connection), DeviceNet
31.3
X6 - M12 circular connector, 4-pole (operating
voltage)
Pin Wire.color* Configuration
1
brown
+24 V
2
not used
3
blue
GND
4
not used
* The indicated wire colours refer to the connection cable, part no. 918038, available as an accessory.
Table 110:
X6 - M12 circular connector, 4-pole (operating voltage)
2
X3.-.M12.circular.connector,.5-pole.
DeviceNet
3
1
5
4
X5.-.M8.circular.connector,.4-pole..
1
3
(only.Type.8693).
Input signals
Process actual value
4
2
2
X6.-.M12.circular.connector,.4-pole.
1
3
Operating voltage
4
Earthing screw (TE)
Switch (to operate loosen the screw connection)
Color
not used
not used
not used
white
blue
On.the.device.side External.circuit./.Signal.level
1
3
Configuration
2
1
3
5
4
24 V DC ± 10 %
max. residual ripple 10%
english
213