Cal.user - Calibration Of Actual Value And Set-Point Value - Burkert 8692 Operating Instructions Manual

Electropneumatic positioner and process controller
Table of Contents

Advertisement

25.2.15 C AL.USER – Calibration of actual value and set-point value
The following values can be manually calibrated with this function:
• Position actual value calibr. POS (0 - 100 %)
• Position set-point value
For the calibration process the signal type is displayed which was specified for the input signal.
See chapter "22.2 INPUT - Setting the input signal".
Type.8693:
The following values can be calibrated only for Type 8693 and activated process controller (P.CONTROL).
• Process set-point value
For the calibration process the signal type is displayed which was specified for the input signal.
See chapter "22.2 INPUT - Setting the input signal".
The calibration of the process set-point value is only possible if the external set-point value default was
selected when setting up the process controller.
See chapter "24.2.3 SP-INPUT – Type of the set-point value default (internal or external)".
Setting: P.CONTROL → SETUP → SP-INPUT → extern
• Process actual value
For the calibration process the signal type is displayed which was specified for the process actual value when
setting up the process controller.
See chapter "24.2.1 PV-INPUT – Specifying signal type for the process actual value"
The frequency signal type (flow rate) cannot be calibrated.
If the frequency was set when setting up the process controller (P.CONTROL → SETUP → PV-INPUT
→ Frequenz), the calibr. PV menu option is hidden.
136
calibr. INP
(4 - 20 mA, 0 - 20 mA, 0 - 5 V, 0 - 10 V)
calibr. SP
(4 - 20 mA, 0 - 20 mA, 0 - 5 V, 0 - 10 V)
calibr. PV
(4 - 20 mA or *C)
english
Type 8692, 8693
Auxiliary functions