Type 8692, 8693
Start-Up
Possible.error.messages.when.running P.TUNE:
Display
Cause of fault
TUNE
Manual termination of self-optimization by
err/break
pressing the
P.TUNE
No supply pressure connected.
ERROR 1
No change to process variable.
Table 50:
P.TUNE; possible error messages
After making all the settings described in chapter "Start-Up", the process controller is ready for use.
Activation and configuration of auxiliary functions is described in the following chapter "25 Configuring the aux-
iliary functions".
key.
EXIT
Remedial action
Connect supply pressure.
Check process and, if required, switch on
pump or open the shut-off valve.
Check process sensor.