Type 8692, 8693
Auxiliary functions
If several diagnosis messages are available with different status signals, the status signal with the highest priority
is shown on the display.
Overview.of.the.status.signals.according.to.NE.107.(NE.=.NAMUR.recommendation):.
Priority
1
Status.signal
Description
Failure
Table 76:
CONFIG.MSG; overview of status signals
The following status signals have been preset at the factory for the messages of the diagnosis functions:
Diagnosis.function
SERVICE.TIME
TRAVEL.ACCU
CYCLE.COUNTER
TEMP.CHECK
STROKE.CHECK
PV.MONITOR
POS.MONITOR
Table 77:
CONFIG.MSG; factory setting (Default)
Assignment.of.status.signals:
Key
Action
/
Select CONFIG.MSG
ENTER
Press
/
Select required diagnosis
function
ENTER
Press
/
Select required status signal
SELEC
Press
EXIT
Press
EXIT
Press
Table 78:
CONFIG.MSG; assignment of status signals
2
Function check
Status.signal.according.to.NE.107
Maintenance required
Maintenance required
Maintenance required
Out of specification
Out of specification
Out of specification
Out of specification
Description
All activated diagnosis functions, which can output a message, are
displayed.
The list of possible status signals is displayed.
The selected status signal is now marked by a filled circle
Acknowledgment and simultaneous return to the CONFIG.MSG
menu.
The status signal is now assigned to the diagnosis function.
Return to the DIAGNOSE main menu.
3
4
Out of specification
Maintenance required
Signal.
Miniature
english
Priority
4
4
4
3
3
3
3
.
155