The addresses indicated in "Table 114" can be used as a path data for the attribute Produced Connection Path of
an I/O connection.
The attributes described in more detail in the following "Table 115"can be transferred as input process data via this
I/O connection.
Nevertheless, by using this address data, the attributes combined in the assemblies can also be accessed acycli-
cally via Explicit Messages.
Name
POS
CMD
PV *
SP *
ERR
* relevant only for Type 8693 and when process controller activated.
Table 115:
Input data attributes; DeviceNet
220
Description.of.the.input.data.attributes
Actual position
Actual value of positioner as ‰. Value range 0 – 1000. However,
values <0 or >1000 also possible if e.g. Autotune has not run
through correctly.
Set-point position
Set-point value of positioner as ‰. Value range 0 – 1000.
Process actual value (process value)
Actual value of process controller in physical unit (as set in the
menu P.CONTROL → SETUP → PV-INPUT or PV-SCALE), max.
value range -999 – 9999, depending on internal scaling.
Process set-point value
Set-point value of process controller in physical unit (as set in the
menu P.CONTROL → SETUP → SP-INPUT or SP-SCALE), max.
value range -999 – 9999, depending on internal scaling.
Error
Indicates the number of the process value (output) which was not
written. The value is retained until it is deleted with "1" by acyclically
writing the "Error" attribute (access via Explicit Message – Set
Attribute Single).
HEX
0X14 INP
0X15 SP
english
Type 8692, 8693
DeviceNet
Attribute.Address.Class,.
Instance,.Attribute;.
Data.type,.Length
111, 1, 59;
INT, 2 byte
111, 1, 58;
UINT, 2 byte
120, 1, 3;
INT, 2 byte
120, 1, 2;
INT, 2 byte
100, 1, 1;