Electropneumatic positioner and process controller
Table of Contents

Advertisement

Type 8692, 8693
Start-Up
24.2
SETUP – Setting up the process controller
These functions specify the type of control.
The procedure is described in the following chapters "24.2.1" to "24.2.5".
24.2.1 PV-INPUT – Specifying signal type for the process actual
value
One of the following signal types can be selected for the process actual value:
• Standard signal
• Frequency signal
• Circuit with Pt 100
Factory setting: 4 ... 20 mA
Operating structure:
PV-INPUT
ENTER
EXIT
Figure 45:
Operating structure PV-INPUT
Specifying.signal.type.in.the.menu.SETUP.→.PV-INPUT:
Key
Action
/
Select PV-INPUT
ENTER
Press
/
Select signal type
SELEC
Press
EXIT
Press
Table 37:
PV-INPUT; specifying signal type
4 ... 20 mA
flow rate, pressure, level
0 ... 1000 Hz
flow rate
-20 °C ... +220 °C
temperature
SELEC
Standard signal 4–20 mA
4-20 mA
(flow rate, pressure, level)
Frequency signal 0 ... 1000 Hz
Frequenz
(flow rate)
Circuit with Pt 100
PT 100
(temperature) -20 °C ... +220 °C
Description
The signal types are displayed.
The selected signal type is now marked by a filled circle
Return to SETUP.
.