X6 - M12 Circular Connector, 4-Pole (Operating Voltage); X4 - M8, 4-Pole Socket (Proximity Switch) - Option Only - Burkert 8692 Operating Instructions Manual

Electropneumatic positioner and process controller
Table of Contents

Advertisement

Type 8692, 8693
Installation
Pin Wire.color* Configuration
Output.signals.to.the.control.centre.(e.g..PLC).
(required.for.analogue.output.and/or.binary.output.option.only)
6
pink
Analog position feedback +
5
gray
Analog position feedback GND
4
yellow
Binary output 1
3
green
Binary output 2
2
brown
Binary outputs GND
* The indicated wire colours refer to the connection cable, part no. 919061, available as an accessory.
Table 11:
X1 - M12 circular connector, 8-pole
13.1.3 X6 - M12 circular connector, 4-pole (operating voltage)
Pin Wire.color* Configuration
1
brown
+24 V
2
not used
3
blue
GND
4
not used
* The indicated wire colours refer to the connection cable, part no. 918038, available as an accessory.
Table 12:

X6 - M12 circular connector, 4-pole (operating voltage)

13.1.4 X4 - M8, 4-pole socket (proximity switch) - option only
Pin
Wire.color*
Configuration
1
brown
Proximity switch 1 out
2
white
GND
3
blue
+24 V DC
4
not used
* The indicated wire colours refer to the connection cable, part no. 92903475, available as an accessory.
Table 13:
X4 - M8, 4-pole socket, proximity switch
On.the.device.side External.circuit./.Signal.level
6
+ (0/4 ... 20 mA or 0 ... 5 / 10 V)
for operating voltage, galvanically
isolated
5
GND Analog feedback
4
24 V / 0 V
3
24 V / 0 V
2
GND
On.the.device.side External.circuit./.Signal.level
1
24 V DC ± 10 %
max. residual ripple 10%
3
On.the.device.
External.circuit./.Signal.level
side
1
2
Proximity switch
3
english
51

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

8693

Table of Contents