Auxiliary functions
25.2.5 S PLTRNG – Signal split range
Min. and max. values of the input signal as % for which the valve runs through the entire stroke range.
Factory setting:
Min = 0 %;
Type.8693: The SPLTRNG auxiliary function can only be selected when operating as a positioner
(position controller).
P.CONTROL = not activated.
Use this auxiliary function to limit the position set-point value range of the Type 8692/8693 by specifying a minimum
and a maximum value.
As a result, it is possible to divide a utilised standard signal range (4 – 20 mA; 0 – 20 mA; 0 – 10 V or 0 – 5 V) into
several devices (without or with overlapping).
This allows several valves to be used alternately or in the case of overlapping set-point value ranges simultane-
ously as actuating element.
SPLTRNG
ENTER
EXIT
* If the submenu is left by pressing the
Figure 71:
Operating structure SPLTRNG
The changed data is saved in the memory (EEPROM) only when there is a switch to the process level,
by leaving the main menu (MAIN) using the left selection key
symbol is indicated
Splitting.a.standard.signal.range.into.two.set-point.value.ranges
Valve stroke [%] (POS)
100
4
Set-point value range
Positioner 1
Figure 72:
Graph - SPLTRNG
Max = 100 %
Min
0 %
INPUT
Max 100 %
INPUT
ESC
key, the value remains unchanged.
on the display.
6
8
10
12
14
16
Set-point value range
Positioner 2
Input the minimum value of the
Enter
input signal as %.
value
Adjustment range: 0 – 75 %
Input the maximum value of the
Enter
input signal as %.
value
Adjustment range: 25 – 100 %
*
OK
EXIT
. During the save process, the save
Set-point value [mA]
18
20
(INP)
english
119