Configuration.of.the.process.data; Static Input Assemblies - Burkert 8692 Operating Instructions Manual

Electropneumatic positioner and process controller
Table of Contents

Advertisement

Type 8692, 8693
DeviceNet
32.4
Configuration of the process data
The following components are required for the configuration:
• Software suitable for the configuration. For example RSNetWorx for DeviceNet (Rev. 4.12.00).
• EDS file (is on the supplied CD)
Implementation of the configuration process is described in the following chapters "32.5 Configuration example 1"
and "32.6 Configuration example 2".
Transmitting.process.data.
To transmit process data via an I/O connection, 5 static input and 2 static output assemblies can be selected.
These assemblies contain selected attributes combined into one object so that process data can be transmitted
collectively via an I/O connection.
Selecting the process data
The process data is selected by setting the device parameters during initialization of an I/O connection according
to the DeviceNet specification. The following device parameters can be set:
• Active Input Assembly and Active Output Assembly or
• Produced Connection Path and Consumed Connection Path
- if supported by the DeviceNet Master/Scanner -.
32.4.1 Static input assemblies
Name
POS+ERR
(factory setting)
POS+CMD+ERR
PV+ERR
PV+SP+ERR
PV+SP+CMD+ERR
Table 114:
Static input assemblies, DeviceNet
Address.of.data.attribute.of.the.assemblies.
for.read.access..Class,.Instance,.Attribute
4, 1, 3
4, 2, 3
4, 3, 3
4, 4, 3
4, 5, 3
Format.of.the.data.attribute
Byte 0: POS low
Byte 1: POS high
Byte 2: ERR
Byte 0: POS low
Byte 1: POS high
Byte 2: CMD low
Byte 3: CMD high
Byte 4: ERR
Byte 0: PV low
Byte 1: PV high
Byte 2: ERR
Byte 0: PV low
Byte 1: PV high
Byte 2: SP low
Byte 3: SP high
Byte 4: ERR
Byte 0: PV low
Byte 1: PV high
Byte 2: SP low
Byte 3: SP high
Byte 4: CMD low
Byte 5: CMD high
Byte 6: ERR
english
219