31
ELECTRICAL CONNECTIONS
DANGER!
Risk.of.injury.due.to.electrical.shock!
▶ Before reaching into the device or the equipment, switch off the operating voltage and secure to prevent
reactivation!
▶ Observe applicable accident prevention and safety regulations for electrical equipment!
WARNING!
Risk.of.injury.from.improper.installation!
▶ Installation may be carried out by authorized technicians only and with the appropriate tools!
Risk.of.injury.from.unintentional.activation.of.the.system.and.an.uncontrolled.restart!
▶ Secure system from unintentional activation.
▶ Following installation, ensure a controlled restart.
For operation of the device the following must always be connected:
→
X6 - circular connector M12, 8-pole
(for operating voltage see "Table 110: X6 - M12 circular connector, 4-pole (operating voltage)")
and
→
X3 - circular connector M12, 5-pole,
(see "Table 109: X3 - M12 circular connector, 5 pole (bus connection), DeviceNet")
Procedure:
→
Connect Type 8692/8693 according to the tables.
On the electrical connection housing is a setscrew with nut for connection of the technical earth.
(see "Figure 132: Electrical connection DeviceNet, Type 8692/8693").
→
Connect setscrew to a suitable grounding point. To ensure electromagnetic compatibility (EMC), ensure that
the cable is as short as possible (max. 30 cm, Ø 1,5 mm
When the operating voltage is applied, Type 8692/8693 is operating.
→
Now make the required basic settings and adjustments for the positioner/process controller.
See chapter "32.2 Start-up sequence" .
NOTE!
Electromagnetic.compatibility.(EMC).is.only.ensured.if.the.appliance.is.connected.correctly.to.an.
earthing.point.
On the outside of the housing is a TE terminal for connection of the technical earth (TE).
• Connect the TE terminal to the earthing point via a shortest possible cable (maximum length 30 cm).
212
english
Type 8692, 8693
DeviceNet
).
2