Dir.act - Sense Of Effective Direction Of The Actuating Drive - Burkert 8692 Operating Instructions Manual

Electropneumatic positioner and process controller
Table of Contents

Advertisement

25.2.4 D IR.ACT – Sense of effective direction of the actuating
drive
Use this auxiliary function to set the sense of effective direction between the aeration state of the actuator and the
actual position (POS).
Factory setting: Rise
DIR.ACT
ENTER
EXIT
Figure 69:
Operating structure DIR.ACT
If the Fall function is selected, the description of the arrow keys (on the display) changes in the MANUAL
operating state
OPN
The changed data is saved in the memory (EEPROM) only when there is a switch to the process level,
by leaving the main menu (MAIN) using the left selection key
symbol is indicated
Actual position
(POS)
deaerated
Figure 70:
Graph - DIR.ACT
118
Rise
Fall
and
CLS
CLS
OPN
on the display.
aerated
english
Direct effective direction
SELEC
(deaerated → 0 %; aerated 100 %)
Inverse effective direction
(deaerated → 100 %; aerated 0%)
. During the save process, the save
EXIT
Aeration state
Type 8692, 8693