25.3.1 Description of the menu for the manual configuration of
X.TUNE
X.TUNE.CONFIG
M.TUNE.POS
M.TUNE.PWM
M.TUNE.AIR
25.3.1.1.
X.TUNE.CONFIG – Configuration of the X.TUNE function
In this menu you can specify which functions are to be executed when the X.TUNE function is running
automatically.
Specifying.the.functions.in.X.TUNE.CONFIG
Key
Action
/
Select X.TUNE.CONFIG
ENTER
Press
/
Select required function
SELEC
Press
EXIT
Press
Table 94:
X.TUNE.CONFIG; specifying the functions for automatic self-parameterization by X.TUNE
172
Configuration.of.the.X.TUNE.
function
Position.of.the.end.positions
Optimization.of.the.PWM.signals Manual optimization of the PWM signals for control
Determination.of.the.opening.
and.closing.times.of.the.actuator
Description
The functions for automatic self-parameterization by X.TUNE are
displayed.
Activate the function by checking the box
Select all required functions in succession using the arrow
keys
activate by checking the box
Return to the Manual.TUNE menu.
english
Specify which functions are to be executed when
X.TUNE is running (automatic self-optimization).
- Specify whether the pneumatic actuator has
mechanical end positions.
- Manual specification of the end positions
If there are no mechanical end positions available,
these are not approached by the X.TUNE and must
be manually specified.
of the aeration valves and bleed valves.
For optimization the valves must be aerated and
bled. A progress bar on the display indicates the
speed at which the valve is aerated or bled.
The setting is optimum when the progress bar
moves as slowly as possible.
Continuous determination of the opening and
closing times of the actuator.
/
and
.
Type 8692, 8693
Auxiliary functions
.