Electrical.data - Burkert 8692 Operating Instructions Manual

Electropneumatic positioner and process controller
Table of Contents

Advertisement

Temperature range control medium 0 ... + 50 °C
Pressure range control medium
Air flow rate pilot valve
Connections
10.8
Electrical data
WARNING!
Only circuits with limited power may be used for UL approved components according to "NEC Class 2".
Protection class
Connections
Pilot valve
Operating voltage
Power consumption
Input data for actual value signal
4 ... 20 mA:
Frequency:
Pt 100:
Input data for set-point value signal
0/4 ... 20 mA:
0 ... 5/10 V:
Analogue feedback
Max. current
Burden (load)
Inductive proximity switches
30
3 ... 7 bar
7 l
/ min (for aeration and deaeration)
N
(Q
- value according to definition for pressure drop from 7 to 6 bar absolute)
Nn
optional: 130 l
connections)
Plug-in hose connector ø 6 mm /
1/4" socket connection G1/8
3 as per DIN EN 61140 (VDE 0140-1)
Cable gland M16 x 1.5, SW22 (clamping area 5 ... 10 mm)
with connection terminals for cable cross-sections 0.14 ... 1.5 mm²
(24 V DC) or
circular plug-in connector (M12 x 1) (24 V DC, PROFIBUS DP, DeviceNet)
24 V DC ± 10 %, max. residual ripple 10 %
< 5 W
Input resistance
Resolution
Measurement range
Input resistance
Resolution
Input signal
Waveform
Measurement range
Resolution
Measurement current
Input resistance
Resolution
Input resistance
Resolution
10 mA (for voltage output 0 ... 5/10 V)
0 ... 560 Ω (for current output 0/4 ... 20 mA)
100 mA current limitation
english
/ min (for aeration and deaeration) (only single-acting
N
180 Ω
12 bit
0 ... 1000 Hz
17 kΩ
1‰ of measurement value
> 300 mVss
sine, square, triangle
-20 ... +220 °C
< 0.1 °C
< 1 mA
180 Ω
12 bit
19 kΩ
12 bit
Type 8692, 8693
Description of System

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

8693

Table of Contents