Burkert 8692 Operating Instructions Manual page 139

Electropneumatic positioner and process controller
Table of Contents

Advertisement

Type 8692, 8693
Auxiliary functions
25.2.15.2. Calibration of the process set-point value and process actual
value
Key
Action
MENU
Press
for approx. 3 s
/
Select CAL.USER
ENTER
calibr. SP - calibration of the process set-point value:
/
Select calibr.SP
ENTER
Press
Select SP 0mA (4mA/0V)
/
-
-
OK
Press
/
Select SP 20mA (5V/10V)
-
-
OK
Press
EXIT
Press
calibr. PV - calibration of the process actual value for input signal 4 - 20 mA:
/
Select calibr.PV
ENTER
Press
/
Select PV 4mA
-
-
OK
Press
/
Select PV 20mA
-
-
OK
Press
EXIT
Press
calibr. PV - calibration of the process actual value for input signal Pt 100:
/
Select calibr.PV
ENTER
Press
/
Select decimal place
Increase number
OK
Press
EXIT
Press
EXIT
Press
Table 64:
CAL.USER; calibration of position actual value and position set-point value
Description
Switching from process level
(To do this, the auxiliary function must be incorporated into the main
menu).
The submenu options are displayed.
The menu options for the minimum and the maximum process set-
point values are displayed.
The minimum value for the input signal is displayed.
Apply the minimum value to the input.
Transfer and simultaneous return to the calibr.SP menu.
The maximum value for the input signal is displayed.
Apply the maximum value to the input.
Transfer and simultaneous return to the calibr.SP menu.
Acknowledgment and simultaneous return to the CAL.USER menu.
The menu options for the minimum and the maximum process actual
values are displayed.
The minimum value for the input signal is displayed.
Apply the minimum value to the input.
Transfer and simultaneous return to the calibr.PV menu.
The maximum value for the input signal is displayed.
Apply the maximum value to the input.
Transfer and simultaneous return to the calibr.PV menu.
Acknowledgment and simultaneous return to the CAL.USER menu.
The input screen for calibration of the temperature is opened.
Input the current temperature.
Transfer and simultaneous return to the CAL.USER menu.
Acknowledgment and simultaneous return to the main menu (MAIN).
Switching from setting level
setting level.
process level.