Type 8692, 8693
Auxiliary functions
25.3.1.2.
X.TUNE.POS – Setting of the end positions
In this menu you can specify whether the pneumatic actuator has mechanical end positions or not.
If there are no mechanical end positions available, these are not approached by the X.TUNE and must be man-
ually specified.
Position.of.the.end.positions
Key
Action
/
Select M.TUNE.POS
ENTER
Press
If.mechanical.end.positions.are.available
/
Select ACT.limit
SELEC
Press
EXIT
Press
If.mechanical.end.positions.are.not.available
/
Select ACT.nolimit
SELEC
Press
/
Select POS.pMIN
INPUT
Press
/
OPN
Open more
Close more
CLS
OK
Press
/
Select POS.pMAX
INPUT
Press
/
OPN
Open more
Close more
CLS
OK
Press
EXIT
Press
EXIT
Press
Table 95:
M.TUNE.POS; position of the end positions
Description
The selection for
ACT.limit = mechanical end positions available
ACT.nolimit = mechanical end positions not available
is displayed.
The selection is marked by a filled circle
Return to the Manual.TUNE menu.
The CAL.POS submenu for inputting the end positions is opened.
The input screen for the value of the lower end position is opened.
Approach lower end position of the valve.
Transfer and simultaneous return to the CAL.POS menu.
The input screen for the value of the upper end position is opened.
Approach upper end position of the valve.
Transfer and simultaneous return to the CAL.POS menu.
Return to the M.TUNE.POS. menu.
Return to the Manual.TUNE menu.
.
english
173