X.tune.config - Manual Configuration Of X.tune - Burkert 8692 Operating Instructions Manual

Electropneumatic positioner and process controller
Table of Contents

Advertisement

Type 8692, 8693
Start-Up
X.TUNE
Compressed air failed during Autotune
ERROR 2
(X.TUNE).
X.TUNE
Actuator or control system deaeration side
ERROR 3
leaking
X.TUNE
Control system aeration side leaking
ERROR 4
X.TUNE
The end positions for POS-MIN and
ERROR 6
POS-MAX are too close together
X.TUNE
Incorrect assignment POS-MIN and
ERROR 7
POS-MAX
Table 34:
X.TUNE; possible error messages
After making the settings described in chapters "22.2" and "22.3", the positioner (position controller) is ready for
use.
Activation and configuration of auxiliary functions is described in the following chapter "25 Configuring the aux-
iliary functions".
22.3.1 X.TUNE.CONFIG – Manual configuration of X.TUNE
This.function.is.needed.for.special.requirements.only.
For standard applications the X.TUNE function (automatic adjustment of the positioner), as described
above, is run using the factory default settings.
The description of the X.TUNE.CONFIG function can be found in chapter "25.3 Manual configuration of X.TUNE".
Check compressed air supply
Not possible, device defective
Not possible, device defective
Check compressed air supply
To determine POS-MIN and POS-MAX,
move the actuator in the direction indi-
cated on the display.
English
85