Key
Action
/
<
OK
Press
/
Select TEMP.MIN
INPUT
Press
/
<
OK
Press
EXIT
Press
EXIT
Press
Table 88:
TEMP.CHECK; specifying temperature limit.
STROKE.CHECK –.End.position.monitor
The STROKE.CHECK function is used to monitor the physical end positions of the armature. In this way wear marks
can be detected on the valve seat.
To do this, a tolerance band is specified for the lower end position (position 0 %) and for the upper end position
(position 100 %). If an end position exceeds or falls below the tolerance band, a message is output.
• To do this, a history entry is made in the HISTORY submenu. For description see "25.2.21.7. History entries in
the HISTORY submenu".
• The status signal, which is assigned to the message, is indicated at short intervals on the display.
See also D.MSG and CONFIG.MSG in chapter "25.2.21.5", page 154.
In addition to the monitor there is an end position slave pointer. This indicates the minimum and maximum position
of the determined end positions. The slave pointer can be reset by pressing the
Display.STROKE.CHECK
STROKE.CHECK
MAX
MIN
LIMIT
HISTORY
29-9-1
EXIT
Table 89:
STROKE.CHECK; end position monitor
166
Description
Input upper temperature limit TEMP.MAX.
Increase value
Changing the decimal
place
Acknowledge value.
Open factory setting for lower temperature limit.
Input lower temperature limit TEMP.MIN.
Increase value
Changing the decimal
place
Acknowledge value.
Return to the TEMP.CHECK menu.
Return to the DIAGNOSE main menu.
Description.of.the.functions
MAX indicates the maximum position of the slave pointer
MIN indicates the minimum position of the slave pointer
67.6.%
30. 9 %
The tolerance band for the physical end positions can be set in the LIMIT
submenu. A message is output if the temperature goes outside the per-
mitted range.
Example:
Input upper end position TOL MAX = 1 %
If the position is less than -1 %, a message is output
Input lower end position TOL ZERO = 1 %
If the position is greater than 101 %, a message is output
The history entries of the last 3 messages can be viewed and deleted in
the HISTORY submenu.
english
Type 8692, 8693
Auxiliary functions
CLEAR
key.