Mitsubishi Electric QD75P1N User Manual page 97

Type qd75p/qd75d positioning module
Table of Contents

Advertisement

4
INSTALLATION, WIRING AND MAINTENANCE OF THE PRODUCT
[Applicable connectors]
Mitsubishi Electric 40-pin connector
Model
A6CON1
A6CON2
A6CON4
[Wiring example of shielded cable]
Connector (A6CON1)
To QD75
The length between the connector and the shielded
cables should be the shortest possible.
The table below shows applicable connectors for external devices. When wiring, use
applicable wires and an appropriate tightening torque.
Tightening torque
0.20 to 0.29N • m
The following shows a wiring example for noise reduction in the case where the
connector A6CON1 is used.
To external devices
(for two drive units)
Diameter
Type
2
0.3mm
(22AWG)
0.088 to 0.24mm
2
Stranded
(28 to 24AWG)
0.3mm
2
(22AWG)
Shielded
cable
To external device
To drive unit
Use the shortest possible length to
ground the 2mm
(The shield must be grounded on
the QD75 side.)
4 - 9
MELSEC-Q
Wire
Temperature
Material
rating
Copper
75C or more
Connector
2
or more FG wire.
Drive
unit

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents