5
DATA USED FOR POSITIONING CONTROL
Da.1 Operation pattern
The operation pattern designates whether positioning of a certain data No. is to be
ended with just that data, or whether the positioning for the next data No. is to be
carried out in succession.
[Operation pattern]
.............................................................................
Positioning complete
Continuous positioning with one start signal
Positioning
continued
Continuous path positioning with speed change
1) Positioning complete..................... Set to execute positioning to the designated
2) Continuous positioning control ..... Positioning is carried out successively in
3) Continuous path control ................ Positioning is carried out successively in
Da.2 Control system
Set the "control system" for carrying out positioning control.
Note)
When "JUMP instruction" is set for the control system, the " Da.9
Dwell time" and " Da.10 M code" setting details will differ.
In case you selected "LOOP" as the control system, the " Da.10
M code" should be set differently from other cases.
Refer to CHAPTER 9 "MAJOR POSITIONING CONTROL" for details
on the control systems.
If "degree" is set for " Pr.1 Unit setting", circular interpolation control
or 3-axis helical interpolation control cannot be carried out. The error
"Circular interpolation not possible" (error code: 535) will occur when
executed.
The 3-axis helical interpolation control can be set only for the QD75N
with a serial number (first five digits) of "17102" or later. If the 3-axis
helical interpolation control is set for the QD75N with a serial number
(first five digits) earlier than "17102", the error "Control system setting
error" (error code: 524) will occur.
Da.3 Acceleration time No.
Set which of "acceleration time 0 to 3" to use for the acceleration time during
positioning.
0 : Use the value set in " Pr.9 Acceleration time 0".
1 : Use the value set in " Pr.25 Acceleration time 1".
2 : Use the value set in " Pr.26 Acceleration time 2".
3 : Use the value set in " Pr.27 Acceleration time 3".
Da.4 Deceleration time No.
Set which of "deceleration time 0 to 3" to use for the deceleration time during
positioning.
0 : Use the value set in " Pr.10 Deceleration time 0".
1 : Use the value set in " Pr.28 Deceleration time 1".
2 : Use the value set in " Pr.29 Deceleration time 2".
3 : Use the value set in " Pr.30 Deceleration time 3".
address, and then complete positioning.
order of data Nos. with one start signal.
The operation halts at each position
indicated by a positioning data.
order of data Nos. with one start signal.
The operation does not stop at each
positioning data.
5 - 60
MELSEC-Q
Independent positioning control
(Positioning complete)
..........
Continuous positioning control
.....
Continuous path control