Mitsubishi Electric QD75P1N User Manual page 555

Type qd75p/qd75d positioning module
Table of Contents

Advertisement

12 CONTROL SUB FUNCTIONS
Various operations
PLC READY signal [Y0]
Pr.17 Torque limit setting value
Cd.22 New torque value
Md.35 Torque limit stored value
[3] Control details
The following drawing shows the operation of the torque limit function.
100%
0%
Torque limited at the parameter
torque limit setting value (100%)
100%
Fig. 12.17 Torque limit function operation
[4] Control precautions
(1) When limiting the torque at the " Pr.17 Torque limit setting value", confirm
that " Cd.22 New torque value" is set to "0". If this parameter is set to a
value besides "0", the " Cd.22 New torque value" will be validated, and the
torque will be limited at that value. (Refer to Section 12.5.4 "Torque change
function" for details about the "new torque value".)
(2) When " Pr.54 OPR shift amount" exceeds " Pr.17 Torque limit setting
value", the error "OPR torque limit value error" (error code: 995) will occur.
(3) When the operation is stopped by torque limiting, the droop pulse will remain
in the deviation counter. If a "deviation counter clear" is carried out by
issuing an external signal at this time, positional deviation will occur when
the operation is continued. If the load torque is eliminated, operation for the
amount of droop pulses will be carried out.
50%
0%
Torque limited at the parameter
torque limit setting value (50%)
50%
12 - 31
MELSEC-Q

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents