Mitsubishi Electric QD75P1N User Manual page 695

Type qd75p/qd75d positioning module
Table of Contents

Advertisement

15
TROUBLESHOOTING
Related buffer memory
address
Axis 1 Axis 2 Axis 3 Axis 4
1504 1604 1704 1804
1500 1600 1700 1800
Refer to Section 5.3
"List of positioning data"
ABS setting direction in the
unit of degree
1550 1650 1750 1850
Software stroke limit
upper limit
18
168
318
468
19
169
319
469
Software stroke limit
lower limit
20
170
320
470
21
171
321
471
Refer to Section 5.3
"List of positioning data"
Set range
(Setting with sequence program)
<M code OFF request>
1: M code ON signal is turned OFF
<Positioning start No.>
1 to 600,
7000 to 7004,
9001 to 9004
<Maximum radius>
536870912
<LOOP to LEND>
1 to 65535
0: Shortcut
1: ABS clockwise
2: ABS counterclockwise
• [mm] [inch] [pulse]
–2147483648 to 2147483647
• [degree]
0 to 35999999
0: Use the set value in " Pr.18 M
code ON signal output timing".
1: WITH mode
2: AFTER mode
0: Use the set value in " Pr.20
Interpolation speed designation
method".
1: Composite speed
2: Reference axis speed
<Number of pitch>
0 to 999
After turning OFF the M code ON signal, start the
system. (Refer to Section 12.7.3)
Check the sequence program which turns ON/OFF the
PLC READY signal (Y0), and turn ON the PLC READY
signal. Then start the system.
Check the QD75 READY ON signal, and then start the
system. (Refer to Section 3.3.2)
Normalize the positioning start No.
(Refer to Section 12.7.7)
Correct the positioning data.
(Refer to Section 9.2.10, 9.2.11)
Set 1 to 65535 for number of repetitions of the "LOOP".
(Refer to Section 9.2.22)
• Set the ABS setting direction in the unit of degree
within the setting range.
• Set "0" when the software stroke limits are valid.
(Refer to Section 9.1.5)
Invalidate the software stroke limit.
(To invalidate, set the software stroke limit upper limit
value to the software stroke limit lower limit value.)
(Refer to Section 9.1.5)
Correct the positioning data "M code ON signal output
timing" to 0 to 2.
Correct the positioning data "Interpolation speed
designation method" to 0 to 2.
Correct the number of pitch set in the positioning data
"M code" of the linear interpolation axis to 0 to 999.
15 - 29
MELSEC-Q
Remedy