Disconnect-Style Interposing I/O Terminals; Wiring For Modules With One Group Per Row - GE VersaMax Manual

Table of Contents

Advertisement

2

Disconnect-Style Interposing I/O Terminals,

Wiring for Modules with One Group per Row

This wiring format generally applies when the associated VersaMax module provides for
connection of I/O in 16-point groups. An example of such a module is the VersaMax
24VDC 16pt Output Module, IC200MDL740:
Q1
A
1
When connecting an Interposing Disconnect base in this format, follow these guidelines:
Connect the field devices to A1-A16 (or B1-B16 where appropriate)
Connect the return wires of field devices to the corresponding common connections –
A1 to W1, A2 to W2, A9 to X1, A10 to X2, etc.
Connect jumpers between the A17, W, and X terminals (or B17, Y, and Z)
Connect the power supply between A17 and A18 (or B17 and B18)
Example: Wiring for Output Module IC200MDL740
Example field wiring for IC200CHS101 when used with VersaMax modules with 1 group
per terminal row
2-28
VersaMax® Modules, Power Supplies, and Carriers User's Manual – March 2003
Q4
Q2
Q3
Q5
Q6
Q7
2
3
4
5
6
7
J1
J2
A16 A15 A14 A13 A12 A11 A10 A9
X8
X7
X6
Q8
Q9
Q10 Q11 Q12 Q13 Q14 Q15
8
9
10
11
12
13
A18
A17 X W
A8
A7
A6
A5
A4
A3
A2
A1
X5
X4
X3
X2
X1
W8 W7 W6 W5 W4 W3 W2 W1
Q1
Q16
14
15
16
17
18