Wiring To Control Terminals - GE AF-600 FP Design And Installation Manual

Fan & pump drive
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

Installation
Terminal Parameter
2
2
12, 13
18
19
32
33
27
29
20
39
42
50
53
54
55
61
2-14
Terminal Description
Digital Inputs/Outputs
Default
Setting
Description
-
+24 V DC
24 V DC supply
voltage. Maximum
output current is 200
mA total for all 24 V
loads. Usable for
digital inputs and
external transducers.
E-01
[8] Start
E-02
[0] No
operation
E-05
[0] No
Digital inputs.
operation
E-06
[0] No
operation
E-03
[0] No
Selectable for either
operation
digital input or
output. Default setting
E-04
[14] JOG
is input.
-
Common for digital
inputs and 0 V
potential for 24 V
supply.
Analog Inputs/Outputs
-
Common for analog
output
AN-50
Speed 0 -
Programmable analog
High Limit
output. The analog
signal is 0–20 mA or
4-20 mA at a
maximum of 500 Ω
-
+10 V DC
10 V DC analog
supply voltage. 15 mA
maximum commonly
used for potenti-
ometer or thermistor.
AN-1#
Reference
Analog input.
Selectable for voltage
AN-2#
Feedback
or current. Switches
A53 and A54 select
mA or V.
-
Common for analog
input
Serial Communication
-
Integrated RC filter for
cable shield. ONLY for
connecting the shield
when experiencing
EMC problems.
AF-600 FP Design and Installation Guide
Terminal Parameter
68 (+)
69 (-)
01, 02, 03
04, 05, 06
Table 2.4 Terminal Description

2.5.8.3 Wiring to Control Terminals

Control terminal connectors can be unplugged from the
adjustable frequency drive for ease of installation, as
shown in Figure 2.30.
Figure 2.30 Unplugging Control Terminals
1.
2.
3.
4.
DET-768A
Terminal Description
Digital Inputs/Outputs
Default
Setting
O-3#
O-3#
Relays
E-24 [0]
[0] Alarm
E-24 [1]
[0] Running
Open the contact by inserting a small screwdriver
into the slot above or below the contact, as
shown in Figure 2.31.
Insert the bared control wire into the contact.
Remove the screwdriver to fasten the control wire
into the contact.
Ensure the contact is firmly established and not
loose. Loose control wiring can be the source of
equipment faults or less than optimal operation.
Description
RS-485 Interface. A
control card switch is
provided for
termination resistance.
Form C relay output.
Usable for AC or DC
voltage and resistive
or inductive loads.