9
IC200MDD845
Mixed Module, Output Relay 2.0A Isolated 8 Points
/ Input 24VDC Pos/Neg Logic Grouped 16 Points
Backplane Power Drain per Point
The module's backplane 5 volt power requirement increases as the number of points that
are simultaneously on increases. The chart below shows the relationship between the
number of output points on and the maximum current required.
mA = 46 + (28 x number of output points on)
9-24
VersaMax® Modules, Power Supplies, and Carriers User's Manual – March 2003
Maximum Current Drawn from Backplane (mA)
270
158
46
0
4
Number of Output Points On
8
GFK-1504K