Analog Output Module, 16 Bit Voltage/Current, 1500VAC Isolation, 4 Channels
Wiring Examples
Current Source
Power
Supply
LOAD
Cable Shield Connections
Shielded twisted pair cable is recommended for all of the analog channel connections.
If the module is installed on a Terminal-style I/O Carrier (IC200CHS001, 002, or 005) or
a Compact Terminal-style I/O Carrier (IC200CHS022, 025), the cable shield can be
connected directly to the carrier per the Field Wiring Table. An Auxiliary I/O Terminal
Strip (IC200TBM001, 002, or 005) can also be added to the Terminal-style I/O Carriers to
aid in grounding shields. Be sure to ground the Auxiliary I/O Terminal Strip as well if you
plan to use it for this purpose.
If the module is installed on a Connector-style I/O Carrier (IC200CHS003), the cable
shield can be connected directly to an Interposing Terminal (IC200CHS011, 012, 015).
Be sure to ground the Interposing Terminal. It is recommended to use a shielded
interposing cable as well between the Interposing Terminal and the Connector Base. A
custom shielded cable can be made using the Connector kit (IC200ACC302). In addition,
a custom shield braid can be wrapped around standard Interposing Cables (IC200CBL105,
110, 120, 230). If this approach is used be sure to ground the braid.
All cable shield connections should be connected to earth ground and be kept as short as
practical. The power cable does not need to be shielded.
GFK-1504K
Chapter 11 Analog Output Modules
+
24V
I1+
-
-
I1-
+
IC200ALG331
Current Sink
+
I1+
LOAD
-
+
24V
I1-
Power
Supply
-
11
11-51