GE VersaMax Manual page 151

Table of Contents

Advertisement

7
IC200MDL144
Input Module, 240VAC Isolated 4 Points
Module Specifications
Module Characteristics
Points
Module ID
Isolation:
User input to logic (optical)
and frame ground
Group to group
Point to point
Carrier Requirement
LED indicators
Backplane current
consumption
External power supply
Thermal derating
Input Characteristics
Input voltage
On state voltage
Off state voltage
On state current
Off state current
On response time
Off response time
Input impedance
7-12
VersaMax® Modules, Power Supplies, and Carriers User's Manual – March 2003
4 Isolated Inputs
FFFF8802
500VAC continuous; 2000VAC for 1 minute
None
500VAC continuous; 2000VAC for 1 minute
Requires Box-Style, Barrier-Style or Spring-Style Carrier,
revision B or later. Cannot be used with Connector-Style
Carrier.
One LED per point shows individual point ON/OFF status
OK LED indicates backplane power is present
5V output: 30mA maximum
None
None
0 to 264VAC (47 to 63Hz), 240VAC nominal
155 to 264VAC
0 to 40VAC
7mA minimum
1.5mA maximum
1 cycle maximum
2 cycles maximum
38.5kOhms (reactive) at 60Hz, typical
46.3kOhms (reactive) at 50Hz, typical
GFK-1504K

Hide quick links: