Field Wiring - GE VersaMax Manual

Table of Contents

Advertisement

5
IC200CHS111, Main Base
IC200CHS112, Expansion Base
Relay-Style Interposing I/O Terminals

Field Wiring

Power for operation of the relay coils must be provided by an external 24VDC power
supply. This power must be provided to both the main base and the expansion base.
Connection of this external power supply is made at the terminals A17 & A18 (B17 & B18
for the expansion base). This power connection is for the relay coils only. User loads
must be powered by an external source.
Each relay, status LED and fuse is labeled to indicate the specific point on the VersaMax
output module they are associated with. Components labeled A1-A16 correspond to
points Q1-Q16. Components labeled B1-B16 correspond to points Q17-Q32. Each point
is associated with 3 terminal connections, labeled NO (Normally Open), C (Common), and
NC (Normally Closed). User loads may be connected between C and NO, C and NC, or
both.
5-16
VersaMax® Modules, Power Supplies, and Carriers User's Manual – February 2003
J2
A16
A15
A14
A13
A12
A11
A16
A15
A14
A13
A12
A11
A10
J1
A10
A9
A8
A7
A6
A5
A4
A9
A8
A7
A6
A5
A4
24VDC
-
+
A18
A17
A3
A2
A1
A3
A2
A1
A1
NO C NC
V
Q1
GFK-1504K