Analog Mixed Module, 12 Bit +/-10VDC Input 4 Channels and Output 2 Channels
Jumper Selection
If no jumper is installed outputs hold their last state (the last commanded value from the
backplane) if backplane power or communications are interrupted or the PLC is stopped.
With a jumper installed, if such conditions occur outputs default to 0V. This should only
be changed with field power and backplane power removed.
Wiring Example
Voltage Inputs
Voltage
Source
Voltage
Source
An external source is needed to
power input transceivers.
GFK-1504K
Chapter 12 Analog Mixed I/O Modules
Jumper
Default
None
Hold Last State
JMP 1
Voltage Outputs
Load
V In 1
V In RET 1
Load
V In 4
V In RET 4
Jumper present
selects default to 0
-
24VDC
+
IC200ALG432
0V
V Out 1
V Out RET 1
Shield
V Out 2
V Out RET 2
Shield
JMP 1A
JMP 1B
12
Field Return
Field Power
12-19