Wiring For Modules With Two Groups Per Row - GE VersaMax Manual

Table of Contents

Advertisement

Disconnect-Style Interposing I/O Terminals,

Wiring for Modules with Two Groups per Row

This wiring format generally applies when the associated VersaMax module provides for
connection of I/O in 8-point groups. An example of such a module is the VersaMax
24VDC 16pt Input Module, IC200MDL640:
I1
A
1
When connecting the Interposing Disconnect bases in this format, follow these guidelines:
Connect field devices to A1-A16 (or B1-B16 where appropriate)
Connect return wires of field devices to the corresponding common connections – A1
to W1, A2 to W2, A9 to X1, A10 to X2, etc.
Connect jumpers between the A17, W, and X terminals (or B17, Y, and Z).
Connect power supply between A17 and W (or B17 and Y).
Connect power supply between A18 and X (or B18 and Z).
Example Wiring Diagram for Module IC200MDL640
Example field wiring for IC200CHS101 when used with VersaMax modules with 2 groups
per terminal row
GFK-1504K
Chapter 2 Installation Instructions
-
+
(-)
(+)
I2
I3
I4
I5
I6
I7
2
3
4
5
6
7
J1
J2
A16 A15 A14 A13 A12 A11 A10 A9
X8
X7
+
(-)
I8
I9
I10
11
I12
I13
8
9
10
11
12
13
A18
A17 X W
A8
A7
A6
A5
A4
A3
A2
A1
X6
X5
X4
X3
X2
X1
W8 W7 W6 W5 W4 W3 W2 W1
I1
2
-
(+)
-
-
I14
I15
I16
(+)
(+)
14
15
16
17
18
2-29

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents