Backplane Power Drain Per Point - GE VersaMax Manual

Table of Contents

Advertisement

Backplane Power Drain per Point

The module's backplane 5 volt power requirement increases as the number of points
that are simultaneously on increases. The chart below shows the relationship
between the number of points on and the maximum current required.
GFK-1504K
Chapter 8 Discrete Output Modules
Output Module, Relay 2.0 Amp Isolated Form A 8 Points
mA = 13 + (28 x number of points on)
Maximum Current Drawn from Backplane (mA)
245
128
13
0
Number of Points On
4
8
8
IC200MDL930
8-43