Expansion Transmitter Module Specifications - GE VersaMax Manual

Table of Contents

Advertisement

6
IC200ETM001
Expansion Transmitter Module
Module Specifications
Module Characteristics
Module ID
LED indicators
Backplane current
consumption
Cable Specifications
IC200ERM002:
Maximum cable length
Effective data rate (max)
Electrical Isolation
IC200ERM001:
Maximum cable length
Effective data rate
Electrical Isolation
Firmware Update Interface
Maximum cable length
Effective data rate
Catalog Numbers
Bus Transmitter Module
Expansion Cable
Firmware Update Cable
Terminator Plug
Connector Kit
To make different length expansion cables, purchase the connector kit and use one of
the following commercially-available cables: Belden 8108, Manhattan/CDT M2493,
Alpha 3498C.
6-6
VersaMax® Modules, Power Supplies, and Carriers User's Manual – March 2003
PWR LED indicates 5VDC power status
EXP TX LED indicates expansion bus communication
status
5V output: 44mA maximum
15 meters
5 Mbits/sec
non-isolated differential communications
250 meters (if configured for higher data rate)
750 meters (default distance)
1 Mbits/sec (configurable for cable less than 250 meters)
250 Kbits/sec (default data rate)
500 VDC isolated differential communications
6 feet
See specification for NIU modules (serial lines are pass-
through on ETMs)
IC200ETM001
IC200CBL601 - 1 meter
IC200CBL602 - 2 meters
IC200CBL615 - 15 meters
IC200CBL002
IC200ACC201 (included with ETM)
IC200ACC202
GFK-1504K