11
IC200ALG321
Analog Output Module, 12 Bit Voltage 0 to 10VDC 4 Channels
Jumper Selection
A jumper on the carrier can be used to select the output default mode.
If no jumper is installed on pins B13 and B14 outputs hold their last state (the last
commanded value from the backplane) if backplane power or communications are
interrupted or the PLC is stopped. With a jumper installed, if such conditions occur
outputs default to 0 volts. This should only be changed with field power and backplane
power removed.
Wiring Example
11-12
VersaMax® Modules, Power Supplies, and Carriers User's Manual – March 2003
Jumper
None
JMP 1
Load
Load
Jumper present
selects default to 0
-
24VDC
+
Selects
Hold Last State
Default to 0
VOUT 1
RET 1
Shield
VOUT 4
RET 4
Shield
JMP 1A
JMP 1B
Field Return
Field Power
GFK-1504K