GE VersaMax Manual page 284

Table of Contents

Advertisement

Module Specifications
Module Characteristics
Points
Module ID
Isolation:
User input/output to logic
(optical) and frame ground
Group to group
Point to point
LED indicators
Backplane current consumption
Thermal derating
Input Characteristics
Input voltage
On state voltage
Off state voltage
On state current
Off state current
On response time
Off response time
Input impedance
Output Characteristics
Output voltage
Output voltage drop
Load current
Output leakage current
On response time
Off response time
Protection
Switching frequency
Relay type
Contact type
Contact life
GFK-1504K
Chapter 9 Discrete Mixed Modules
Mixed Module Output Relay 2.0A per Pt Isolated 8 Points /
8 Individually-isolated Form A Relay Outputs
8 Isolated AC Inputs
88048040
250VAC continuous; 1500VAC for 1 minute
250VAC continuous; 1500VAC for 1 minute
Outputs: 250VAC continuous; 1500VAC for 1 minute
Inputs: 250VAC continuous; 1500VAC for 1 minute
One LED per point shows individual point on/off state
OK LED indicates backplane power is present
5V output: 295mA maximum See graph
None
0 to 132VAC (47 to 63Hz), 120VAC nominal
70 to 132VAC
0 to 20VAC
5mA minimum
2.5mA maximum
1 cycle maximum
2 cycles maximum
8.6kOhms (reactive) at 60Hz, typical
10.32kOhms (reactive) at 50Hz, typical
0 to 125VDC, 5/24/125VDC nominal
0 to 265VAC (47 to 63Hz), 120/240VAC nominal
0.3V maximum
10mA per point minimum
2.0 Amps for 5 to 265VAC maximum (resistive)
2.0 Amps for 5 to 30 VDC maximum (resistive)
0.2 Amp for 31 to 125 VDC maximum (resistive)
Not applicable (open contact)
10ms maximum
10ms maximum
No internal fuses or snubbers.
20 cycles per minute (inductive load)
Fixed coil, moving armature
Silver alloy
See appendix B
IC200MDD849
Input 120VAC Isolated 8 Points
9
9-41

Hide quick links:

Advertisement