Wiring For A Box-Style I/O Carrier Or Spring-Style I/O Carrier - GE VersaMax Manual

Table of Contents

Advertisement

2

Wiring for a Box-Style I/O Carrier or Spring-Style I/O Carrier

(IC200CHS002, IC200CHS005)
Field Wiring
Terminals
Each terminal on a Box-Style or Spring-Style I/O Carrier accommodates one solid or
stranded AWG #14 (avg. 2.1mm
wire, or two wires up to AWG #18 (avg. 0.86mm
for 90 degrees C. When inserting two wires in the same position, the wires must be the
same size and type (solid or stranded).
The I/O carrier can accommodate current levels up to 2 Amps per point or 8 Amps per
each power and ground, and a voltage range of up to 264 VAC. Voltage transients up to
300 VAC will not damage the carrier.
For a Box-Style I/O Carrier, recommended terminal torque is .37 to .45 ft-lbs.
The label provided with the module can be folded and inserted in the module's transparent
door.
Terminal Numbering for a Box-Style or Spring-Style I/O Carrier
B1
2-18
VersaMax® Modules, Power Supplies, and Carriers User's Manual – March 2003
2
cross section) to AWG #22 (avg. 0.36mm
A1
A2
A3
A5
A6
A4
B2
B3
B5
B6
B7
B4
2
cross section). Use copper wire rated
A7
A8
A9
A12 A13
A10
A11
B8
B9
B12
B13
B10
B11
2
cross section)
A15 A16
A17
A18
A14
B14
B15 B16
B17
B18
GFK-1504K