GE C30 Instruction Manual

Controller system ur series
Hide thumbs Also See for C30:
Table of Contents

Advertisement

Title Page
GE Multilin
215 Anderson Avenue, Markham, Ontario
Canada L6E 1B3
Tel: (905) 294-6222 Fax: (905) 201-2098
Internet:
http://www.GEmultilin.com
*1601-0088-T2*
C30 Controller System
UR Series Instruction Manual
C30 Revision: 5.6x
Manual P/N: 1601-0088-T2 (GEK-113478A)
Copyright © 2009 GE Multilin
E83849
LISTED
IND.CONT. EQ.
52TL
GE Multilin
834718A2.CDR
I I SO9001:2000
GE Multilin's Quality Management
System is registered to
ISO9001:2000
QMI # 005094
UL # A3775

Advertisement

Table of Contents
loading

Summary of Contents for GE C30

  • Page 1 Title Page GE Multilin C30 Controller System UR Series Instruction Manual C30 Revision: 5.6x Manual P/N: 1601-0088-T2 (GEK-113478A) Copyright © 2009 GE Multilin 834718A2.CDR E83849 I I SO9001:2000 GE Multilin LISTED 215 Anderson Avenue, Markham, Ontario IND.CONT. EQ. 52TL Canada L6E 1B3...
  • Page 3 GE Industrial Systems ADDENDUM This addendum contains information that relates to the C30 Controller System, version 5.6x. This addendum lists a number of information items that appear in the instruction manual GEK-113478A (revision T2) but are not included in the current C30 operations.
  • Page 5: Table Of Contents

    1.3 ENERVISTA UR SETUP SOFTWARE 1.3.1 REQUIREMENTS ....................1-5 1.3.2 INSTALLATION....................1-5 1.3.3 CONFIGURING THE C30 FOR SOFTWARE ACCESS ........1-7 1.3.4 USING THE QUICK CONNECT FEATURE............1-9 1.3.5 CONNECTING TO THE C30 RELAY .............. 1-15 1.4 UR HARDWARE 1.4.1 MOUNTING AND WIRING................
  • Page 6 MANAGED ETHERNET SWITCH MODULE HARDWARE......3-40 3.4.3 MANAGED SWITCH LED INDICATORS ............3-41 3.4.4 CONFIGURING THE MANAGED ETHERNET SWITCH MODULE ....3-41 3.4.5 UPLOADING C30 SWITCH MODULE FIRMWARE .........3-43 3.4.6 ETHERNET SWITCH SELF-TEST ERRORS...........3-46 4. HUMAN INTERFACES 4.1 ENERVISTA UR SETUP SOFTWARE INTERFACE 4.1.1 INTRODUCTION ....................4-1...
  • Page 7 SELECTOR SWITCHES..................6-6 6.2.10 DIGITAL COUNTERS ..................6-6 6.2.11 FLEX STATES ....................6-6 6.2.12 ETHERNET......................6-6 6.2.13 DIRECT INPUTS....................6-7 6.2.14 DIRECT DEVICES STATUS................6-7 6.2.15 EGD PROTOCOL STATUS ................6-8 6.2.16 TELEPROTECTION CHANNEL TESTS ............6-8 GE Multilin C30 Controller System...
  • Page 8 B.4.2 DATA FORMATS..................... B-46 C. IEC 61850 C.1 OVERVIEW C.1.1 INTRODUCTION ....................C-1 COMMUNICATIONS C.1.2 COMMUNICATION PROFILES ................. C-1 C.2 SERVER DATA ORGANIZATION C.2.1 OVERVIEW ....................... C-2 C.2.2 GGIO1: DIGITAL STATUS VALUES ..............C-2 viii C30 Controller System GE Multilin...
  • Page 9 BINARY AND CONTROL RELAY OUTPUT ............E-9 E.2.3 COUNTERS .....................E-10 E.2.4 ANALOG INPUTS ....................E-11 F. MISCELLANEOUS F.1 CHANGE NOTES F.1.1 REVISION HISTORY ..................F-1 F.1.2 CHANGES TO THE C30 MANUAL..............F-2 F.2 ABBREVIATIONS F.2.1 STANDARD ABBREVIATIONS ................. F-5 GE Multilin C30 Controller System...
  • Page 10 TABLE OF CONTENTS F.3 WARRANTY F.3.1 GE MULTILIN WARRANTY................F-7 INDEX C30 Controller System GE Multilin...
  • Page 11: Cautions And Warnings

    For product information, instruction manual updates, and the latest software updates, please visit the GE Multilin web- site at http://www.GEmultilin.com. If there is any noticeable physical damage, or any of the contents listed are missing, please contact GE Multilin immediately.
  • Page 12: Introduction To The Ur

    This new generation of equipment must also be easily incorporated into automation systems, at both the station and enterprise levels. The GE Multilin Universal Relay (UR) has been developed to meet these goals. C30 Controller System...
  • Page 13: Hardware Architecture

    (dual) ring configuration. This feature is optimized for speed and intended for pilot- aided schemes, distributed logic applications, or the extension of the input/output capabilities of a single relay chassis. GE Multilin C30 Controller System...
  • Page 14: Ur Software Architecture

    Employing OOD/OOP in the software architecture of the C30 achieves the same features as the hardware architecture: modularity, scalability, and flexibility. The application software for any UR-series device (for example, feeder protection, transformer protection, distance protection) is constructed by combining objects from the various functionality classes.
  • Page 15: Requirements

    Video capable of displaying 800 x 600 or higher in high-color mode (16-bit color) • RS232 and/or Ethernet port for communications to the relay The following qualified modems have been tested to be compliant with the C30 and the EnerVista UR Setup software. • US Robotics external 56K FaxModem 5686 •...
  • Page 16 Install Software window as shown below. Select the “Web” option to ensure the most recent software release, or select “CD” if you do not have a web connection, then click the Add Now button to list software items for the C30.
  • Page 17: Configuring The C30 For Software Access

    OVERVIEW The user can connect remotely to the C30 through the rear RS485 port or the rear Ethernet port with a PC running the EnerVista UR Setup software. The C30 can also be accessed locally with a laptop computer through the front panel RS232 port or the rear Ethernet port using the Quick Connect feature.
  • Page 18 SERIAL PORTS 10. Click the Read Order Code button to connect to the C30 device and upload the order code. If an communications error occurs, ensure that the EnerVista UR Setup serial communications values entered in the previous step corre- spond to the relay setting values.
  • Page 19: Using The Quick Connect Feature

    MODBUS PROTOCOL 11. Click the Read Order Code button to connect to the C30 device and upload the order code. If an communications error occurs, ensure that the three EnerVista UR Setup values entered in the previous steps correspond to the relay setting values.
  • Page 20 C30. This ensures that configuration of the EnerVista UR Setup software matches the C30 model number. b) USING QUICK CONNECT VIA THE REAR ETHERNET PORTS To use the Quick Connect feature to access the C30 from a laptop through Ethernet, first assign an IP address to the relay from the front panel keyboard.
  • Page 21 Right-click the Local Area Connection icon and select Properties. Select the Internet Protocol (TCP/IP) item from the list provided and click the Properties button. Click on the “Use the following IP address” box. GE Multilin C30 Controller System 1-11...
  • Page 22 1.3 ENERVISTA UR SETUP SOFTWARE 1 GETTING STARTED Enter an IP address with the first three numbers the same as the IP address of the C30 relay and the last number dif- ferent (in this example, 1.1.1.2). Enter a subnet mask equal to the one set in the C30 (in this example, 255.0.0.0).
  • Page 23 If this computer is used to connect to the Internet, re-enable any proxy server settings after the laptop has been discon- nected from the C30 relay. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE enerVista CD or online from http://www.GEmultilin.com). See the Software Installation section for installation details.
  • Page 24 Each time the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct communica- tions to the C30. This ensures that configuration of the EnerVista UR Setup software matches the C30 model number. When direct communications with the C30 via Ethernet is complete, make the following changes: From the Windows desktop, right-click the My Network Places icon and select Properties to open the network con- nections window.
  • Page 25: Connecting To The C30 Relay

    The EnerVista UR Setup software has several new quick action buttons that provide users with instant access to several functions that are often performed when using C30 relays. From the online window, users can select which relay to interro- gate from a pull-down window, then click on the button for the action they wish to perform. The following quick action func- tions are available: •...
  • Page 26: Mounting And Wiring

    Figure 1–7: RELAY COMMUNICATIONS OPTIONS To communicate through the C30 rear RS485 port from a PC RS232 port, the GE Multilin RS232/RS485 converter box is required. This device (catalog number F485) connects to the computer using a “straight-through” serial cable. A shielded twisted-pair (20, 22, or 24 AWG) connects the F485 converter to the C30 rear communications port.
  • Page 27: Faceplate Keypad

    LED off. The relay in the “Not Programmed” state will block signaling of any output relay. These conditions will remain until the relay is explicitly put in the “Programmed” state. Select the menu message SETTINGS PRODUCT SETUP INSTALLATION RELAY SETTINGS RELAY SETTINGS: Not Programmed GE Multilin C30 Controller System 1-17...
  • Page 28: Relay Passwords

    Refer to the Changing Settings section in Chapter 4 for complete instructions on setting up security level passwords. NOTE 1.5.6 FLEXLOGIC™ CUSTOMIZATION FlexLogic™ equation editing is required for setting up user-defined logic for customizing the relay operations. See the Flex- Logic™ section in Chapter 5 for additional details. 1-18 C30 Controller System GE Multilin...
  • Page 29: Commissioning

    1.5 USING THE RELAY 1.5.7 COMMISSIONING The C30 requires a minimum amount of maintenance when it is commissioned into service. Since the C30 is a micropro- cessor-based relay, its characteristics do not change over time. As such, no further functional tests are required.
  • Page 30 1.5 USING THE RELAY 1 GETTING STARTED 1-20 C30 Controller System GE Multilin...
  • Page 31: Overview

    Another option provides two 10Base-F fiber optic ports for redundancy. The Ethernet port supports IEC 61850, Modbus TCP, and TFTP protocols, and allows access to the relay via any standard web browser (C30 web pages). The IEC 60870- 5-104 protocol is supported on the Ethernet port. DNP 3.0 and IEC 60870-5-104 cannot be enabled at the same time.
  • Page 32 2.1 INTRODUCTION 2 PRODUCT DESCRIPTION b) STANDARD ORDER CODES The order codes for the horizontal mount units are shown below. Table 2–2: C30 ORDER CODES (HORIZONTAL UNITS) * - F - W/X Full Size Horizontal Mount BASE UNIT Base Unit...
  • Page 33 2 PRODUCT DESCRIPTION 2.1 INTRODUCTION The order codes for the reduced size vertical mount units are shown below. Table 2–3: C30 ORDER CODES (REDUCED SIZE VERTICAL UNITS) * - F Reduced Size Vertical Mount (see note regarding P/R slot below)
  • Page 34 2 PRODUCT DESCRIPTION c) ORDER CODES WITH PROCESS BUS MODULES The order codes for the horizontal mount units with the process bus module are shown below. Table 2–4: C30 ORDER CODES (HORIZONTAL UNITS WITH PROCESS BUS) * - F - W/X...
  • Page 35: Replacement Modules

    Replacement modules can be ordered separately as shown below. When ordering a replacement CPU module or face- plate, please provide the serial number of your existing unit. Not all replacement modules may be applicable to the C30 relay. Only the modules specified in the order codes are available as replacement modules.
  • Page 36 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs CT/VT Standard 4CT/4VT Sensitive Ground 4CT/4VT MODULES Standard 8CT (NOT AVAILABLE FOR THE C30) Sensitive Ground 8CT Standard 4CT/4VT with enhanced diagnostics Sensitive Ground 4CT/4VT with enhanced diagnostics Standard 8CT with enhanced diagnostics Sensitive Ground 8CT with enhanced diagnostics INTER-RELAY COMMUNICATIONS C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode...
  • Page 37 2 Form-A outputs, 1 Form-C output, 2 Form-A (no monitoring) latching outputs, 8 digital inputs CT/VT Standard 4CT/4VT Sensitive Ground 4CT/4VT MODULES Standard 8CT (NOT AVAILABLE FOR THE C30) Sensitive Ground 8CT Standard 4CT/4VT with enhanced diagnostics Sensitive Ground 4CT/4VT with enhanced diagnostics Standard 8CT with enhanced diagnostics Sensitive Ground 8CT with enhanced diagnostics INTER-RELAY COMMUNICATIONS C37.94SM, 1300nm single-mode, ELED, 1 channel single-mode...
  • Page 38: User-Programmable Elements

    Pickup delay: 0.000 to 999999.999 s in steps of 0.001 tual input Dropout delay: 0.000 to 999999.999 s in steps of 0.001 Reset mode: self-reset or latched Timing accuracy: ±3% or ±4 ms, whichever is greater C30 Controller System GE Multilin...
  • Page 39: Irig-B

    1 to 1000 in steps of 1 Unreturned message alarm: Responding to: Rate of unreturned messages in the ring configuration Monitoring message count: 10 to 10000 in steps of 1 Alarm threshold: 1 to 1000 in steps of 1 GE Multilin C30 Controller System...
  • Page 40: Power Supply

    95% voltage drop across the load impedance. Trickle current: approx. 1 to 2.5 mA Operate time: < 0.6 ms FORM-A CURRENT MONITOR Internal Limiting Resistor: 100 Ω, 2 W Threshold current: approx. 80 to 100 mA 2-10 C30 Controller System GE Multilin...
  • Page 41: Ethernet Switch

    2.2.6 COMMUNICATIONS RS232 RS485 ® ® Front port: 19.2 kbps, Modbus 1 or 2 rear ports: Up to 115 kbps, Modbus RTU, isolated together at 36 Vpk Typical distance: 1200 m Isolation: 2 kV GE Multilin C30 Controller System 2-11...
  • Page 42 Shielded twisted pair: 150 m (492 ft.) MAXIMUM STANDARD FAST ETHERNET SEGMENT LENGTHS 10Base-T (CAT 3, 4, 5 UTP): 100 m (328 ft.) 100Base-TX (CAT 5 UTP):100 m (328 ft.) Shielded twisted pair: 150 m (492 ft.) 2-12 C30 Controller System GE Multilin...
  • Page 43: Inter-Relay Communications

    Operating temperature: –40 to 60°C; the LCD contrast may be Pollution degree: impaired at temperatures less than – Overvoltage category: 20°C Ingress protection: IP40 front, IP20 back HUMIDITY Humidity: operating up to 95% (non-condensing) at 55°C (as per IEC60068-2-30 variant 1, 6days). GE Multilin C30 Controller System 2-13...
  • Page 44: Type Tests

    6 day, variant 1 Damped oscillatory IEEE/ANSI C37.90.1 2.5 kV, 1 MHz RF immunity IEEE/ANSIC37.90.2 20 V/m, 80 MHz to 1 GHz Safety UL508 e83849 NKCR Safety UL C22.2-14 e83849 NKCR7 Safety UL1053 e83849 NKCR 2-14 C30 Controller System GE Multilin...
  • Page 45: Production Tests

    Units that are stored in a de-energized state should be powered up once per year, for one hour continuously, to NOTE avoid deterioration of electrolytic capacitors. GE Multilin C30 Controller System 2-15...
  • Page 46 2.2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2-16 C30 Controller System GE Multilin...
  • Page 47: Description

    HORIZONTAL UNITS The C30 Controller System is available as a 19-inch rack horizontal mount unit with a removable faceplate. The faceplate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional user- programmable pushbuttons and LED indicators.
  • Page 48 VERTICAL UNITS The C30 Controller System is available as a reduced size (¾) vertical mount unit, with a removable faceplate. The face- plate can be specified as either standard or enhanced at the time of ordering. The enhanced faceplate contains additional user-programmable pushbuttons and LED indicators.
  • Page 49 RS232 communications port. The relay is secured to the panel with the use of four screws supplied with the relay. 11.015” 7.482” 1.329” 13.560” 15.000” 14.025” 4.000” 9.780” 843809A1.CDR Figure 3–4: C30 VERTICAL DIMENSIONS (ENHANCED PANEL) GE Multilin C30 Controller System...
  • Page 50 UR S RI S UR S RI S Figure 3–5: C30 VERTICAL MOUNTING AND DIMENSIONS (STANDARD PANEL) For details on side mounting C30 devices with the enhanced front panel, refer to the following documents available online from the GE Multilin website. •...
  • Page 51 3 HARDWARE 3.1 DESCRIPTION Figure 3–6: C30 VERTICAL SIDE MOUNTING INSTALLATION (STANDARD PANEL) GE Multilin C30 Controller System...
  • Page 52: Module Withdrawal And Insertion

    The enhanced faceplate can be opened to the left, once the thumb screw has been removed, as shown below. This allows for easy accessibility of the modules for withdrawal. The new wide-angle hinge assembly in the enhanced front panel opens completely and allows easy access to all modules in the C30. C30 Controller System...
  • Page 53 When the clips have locked into position, the module will be fully inserted. All CPU modules except the 9E are equipped with 10/100Base-T or 100Base-F Ethernet connectors. These con- nectors must be individually disconnected from the module before it can be removed from the chassis. NOTE GE Multilin C30 Controller System...
  • Page 54: Rear Terminal Layout

    3.1 DESCRIPTION 3 HARDWARE The 4.0x release of the C30 relay includes new hardware modules.The new CPU modules are specified with codes 9E and higher. The new CT/VT modules are specified with the codes 8F and higher. NOTE All other input and output modules are compatible with the new hardware. Firmware versions 4.0x and higher are only compatible with the new hardware modules.
  • Page 55 3 HARDWARE 3.1 DESCRIPTION Figure 3–11: EXAMPLE OF MODULES IN F AND H SLOTS GE Multilin C30 Controller System...
  • Page 56: Typical Wiring

    CONTACT INPUT W6a CONTACT INPUT U6a CONTACT INPUT W6c CONTACT INPUT U6c COMMON W5b COMMON U5b CONTACT INPUT W7a GE Consumer & Industrial CONTACT INPUT U7a Multilin CONTACT INPUT W7c CONTACT INPUT U7c CONTACT INPUT W8a CONTACT INPUT U8a CONTACT INPUT W8c...
  • Page 57: Dielectric Strength

    (RFI), and electromagnetic interference (EMI). These protective components can be damaged by application of the ANSI/IEEE C37.90 specified test voltage for a period longer than the specified one min- ute. GE Multilin C30 Controller System 3-11...
  • Page 58: Control Power

    (see the Self-test errors section in chapter 7) or control power is lost, the relay will de-energize. For high reliability systems, the C30 has a redundant option in which two C30 power supplies are placed in parallel on the bus.
  • Page 59: Process Bus Modules

    3.2.4 PROCESS BUS MODULES The C30 can be ordered with a process bus interface module. This module is designed to interface with the GE Multilin HardFiber system, allowing bi-directional IEC 61850 fiber optic communications with up to eight HardFiber merging units, known as Bricks.
  • Page 60 CONT OP # VOFF CONT OP # ION CONT OP # IOFF application of the voltage monitor is breaker trip circuit integrity monitoring; a typical application of the current monitor is seal-in of the control command. 3-14 C30 Controller System GE Multilin...
  • Page 61 Fast Form-C ~6a, ~6c 2 Inputs Form-A ~7a, ~7c 2 Inputs Fast Form-C ~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~8a, ~8c 2 Inputs Fast Form-C ~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs GE Multilin C30 Controller System 3-15...
  • Page 62 Not Used ~5a, ~5c 2 Inputs 2 Outputs Solid-State Solid-State ~6a, ~6c 2 Inputs 2 Outputs Not Used Not Used ~7a, ~7c 2 Inputs 2 Outputs Solid-State Solid-State ~8a, ~8c 2 Inputs Not Used 3-16 C30 Controller System GE Multilin...
  • Page 63 3 HARDWARE 3.2 WIRING 842762A2.CDR Figure 3–16: DIGITAL INPUT/OUTPUT MODULE WIRING (1 of 2) GE Multilin C30 Controller System 3-17...
  • Page 64 CONTACT IN CONTACT IN COMMON SURGE 842763A2.CDR Figure 3–17: DIGITAL INPUT/OUTPUT MODULE WIRING (2 of 2) CORRECT POLARITY MUST BE OBSERVED FOR ALL CONTACT INPUT AND SOLID STATE OUTPUT CON- NECTIONS FOR PROPER FUNCTIONALITY. CAUTION 3-18 C30 Controller System GE Multilin...
  • Page 65 There is no provision in the relay to detect a DC ground fault on 48 V DC control power external output. We recommend using an external DC supply. NOTE GE Multilin C30 Controller System 3-19...
  • Page 66 CONTACT INPUT 2 AUTO-BURNISH = ON 842751A1.CDR Figure 3–20: AUTO-BURNISH DIP SWITCHES The auto-burnish circuitry has an internal fuse for safety purposes. During regular maintenance, the auto-burnish functionality can be checked using an oscilloscope. NOTE 3-20 C30 Controller System GE Multilin...
  • Page 67: Transducer Inputs/Outputs

    (5A, 5C, 5D, 5E, and 5F) and channel arrangements that may be ordered for the relay. Wherever a tilde “~” symbol appears, substitute with the slot position of the module. NOTE Figure 3–21: TRANSDUCER INPUT/OUTPUT MODULE WIRING GE Multilin C30 Controller System 3-21...
  • Page 68: Rs232 Faceplate Port

    3.2.7 RS232 FACEPLATE PORT A 9-pin RS232C serial port is located on the C30 faceplate for programming with a personal computer. All that is required to use this interface is a personal computer running the EnerVista UR Setup software provided with the relay. Cabling for the RS232 port is shown in the following figure for both 9-pin and 25-pin connectors.
  • Page 69 MM fiber optic cable 100Base-FX 100Base-T cable 10/100Base-T Copper ports 100Base-T cable 10/100Base-T 110 to 250 V DC 100 to 240 V AC – — Power supply GROUND 842765A5.CDR Figure 3–23: CPU MODULE COMMUNICATIONS WIRING GE Multilin C30 Controller System 3-23...
  • Page 70 To ensure maximum reliability, all equipment should have similar transient protection devices installed. Both ends of the RS485 circuit should also be terminated with an impedance as shown below. Figure 3–24: RS485 SERIAL CONNECTION 3-24 C30 Controller System GE Multilin...
  • Page 71 For optical power budgeting, splices are required every 1 km for the transmitter/receiver pair. When splicing optical fibers, the diameter and numerical aperture of each fiber must be the same. In order to engage or disengage the ST type connec- tor, only a quarter turn of the coupling is required. GE Multilin C30 Controller System 3-25...
  • Page 72 UR-series relays can be synchronized. The IRIG-B repeater has a bypass function to maintain the time signal even when a relay in the series is powered down. Figure 3–26: IRIG-B REPEATER Using an amplitude modulated receiver will cause errors up to 1 ms in event time-stamping. NOTE 3-26 C30 Controller System GE Multilin...
  • Page 73: Description

    3.3.1 DESCRIPTION The C30 direct inputs and outputs feature makes use of the type 7 series of communications modules. These modules are also used by the L90 Line Differential Relay for inter-relay communications. The direct input and output feature uses the communications channels provided by these modules to exchange digital state information between relays.
  • Page 74 These modules are listed in the following table. All fiber modules use ST type connectors. Not all the direct input and output communications modules may be applicable to the C30 relay. Only the modules specified in the order codes are available as direct input and output communications modules.
  • Page 75: Fiber: Led And Eled Transmitters

    1 Channel 2 Channels Figure 3–31: LASER FIBER MODULES When using a laser Interface, attenuators may be necessary to ensure that you do not exceed the maxi- mum optical input power to the receiver. WARNING GE Multilin C30 Controller System 3-29...
  • Page 76: Interface

    Remove the top cover by sliding it towards the rear and then lift it upwards. Set the timing selection switches (channel 1, channel 2) to the desired timing modes. Replace the top cover and the cover screw. 3-30 C30 Controller System GE Multilin...
  • Page 77 For connection to a higher order system (UR- to-multiplexer, factory defaults), set to octet timing (S1 = ON) and set timing mode to loop timing (S5 = OFF and S6 = OFF). GE Multilin C30 Controller System 3-31...
  • Page 78 G.703 line side of the interface while the other lies on the differential Manchester side of the interface. DMR = Differential Manchester Receiver DMX = Differential Manchester Transmitter G7X = G.703 Transmitter G7R = G.703 Receiver 842775A1.CDR Figure 3–36: G.703 DUAL LOOPBACK MODE 3-32 C30 Controller System GE Multilin...
  • Page 79: Rs422 Interface

    1 as shown below. If the terminal timing feature is not available or this type of connection is not desired, the G.703 interface is a viable option that does not impose timing restrictions. GE Multilin C30 Controller System 3-33...
  • Page 80 Figure 3–39: TIMING CONFIGURATION FOR RS422 TWO-CHANNEL, 3-TERMINAL APPLICATION Data module 1 provides timing to the C30 RS422 interface via the ST(A) and ST(B) outputs. Data module 1 also provides timing to data module 2 TT(A) and TT(B) inputs via the ST(A) and AT(B) outputs. The data module pin numbers have been omitted in the figure above since they may vary depending on the manufacturer.
  • Page 81: Rs422 And Fiber Interface

    When using a laser Interface, attenuators may be necessary to ensure that you do not exceed the maxi- mum optical input power to the receiver. WARNING Shield Tx – G.703 Rx – channel 1 Tx + Rx + Surge Fiber channel 2 842778A1.CDR Figure 3–42: G.703 AND FIBER INTERFACE CONNECTION GE Multilin C30 Controller System 3-35...
  • Page 82: Ieee C37.94 Interface

    IEEE C37.94 standard, as shown below. The UR-series C37.94 communication module has six (6) switches that are used to set the clock configuration. The func- tions of these control switches is shown below. 842753A1.CDR 3-36 C30 Controller System GE Multilin...
  • Page 83 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted. Figure 3–43: IEEE C37.94 TIMING SELECTION SWITCH SETTING GE Multilin C30 Controller System 3-37...
  • Page 84: C37.94Sm Interface

    For the internal timing mode, the system clock is generated internally. Therefore, the timing switch selection should be internal timing for relay 1 and loop timed for relay 2. There must be only one timing source configured. 3-38 C30 Controller System GE Multilin...
  • Page 85 Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously. When the clips have locked into position, the module will be fully inserted. Figure 3–44: C37.94SM TIMING SELECTION SWITCH SETTING GE Multilin C30 Controller System 3-39...
  • Page 86: Managed Ethernet Switch Modules

    The type 2S and 2T embedded managed switch modules are supported by UR-series relays containing type 9S CPU mod- ules with revisions 5.5x and higher. The modules communicate to the C30 through an internal Ethernet port (referred to as the UR port or port 7) and provide an additional six external Ethernet ports: two 10/100Base-T ports and four multimode ST 100Base-FX ports.
  • Page 87: Managed Switch Led Indicators

    UR Setup software, the Switch’s Secure Web Management (SWM), or through the console port using CLI. Select the Settings > Product Setup > Communications > Ethernet Switch > Configure IP menu item to open the Ethernet switch configuration window. GE Multilin C30 Controller System 3-41...
  • Page 88 SAVING THE ETHERNET SWITCH SETTINGS TO A SETTINGS FILE The C30 allows the settings information for the Ethernet switch module to be saved locally as a settings file. This file con- tains the advanced configuration details for the switch not contained within the standard C30 settings file.
  • Page 89: Uploading C30 Switch Module Firmware

    NOTE b) SELECTING THE PROPER SWITCH FIRMWARE VERSION The latest switch module firmware is available as a download from the GE Multilin web site. Use the following procedure to determine the version of firmware currently installed on your switch Log into the switch using the EnerVista web interface.
  • Page 90 After saving the settings file, proceed with the firmware upload by selecting Yes to the above warning. Another window will open, asking you to point to the location of the firmware file to be uploaded. 3-44 C30 Controller System GE Multilin...
  • Page 91 If the firmware load was successful, the following window will appear: Note The switch will automatically reboot after a successful firmware file transfer. NOTE Once the firmware has been successfully uploaded to the switch module, load the settings file using the procedure described earlier. GE Multilin C30 Controller System 3-45...
  • Page 92: Ethernet Switch Self-Test Errors

    No setting required; the C30 EQUIPMENT The C30 has not detected the The C30 failed to see the switch module will read the state of a general MISMATCH: Card XXX presence of the Ethernet on power-up, because switch won’t...
  • Page 93: Human Interfaces

    To start using the EnerVista UR Setup software, a site definition and device definition must first be created. See the EnerV- ista UR Setup Help File or refer to the Connecting EnerVista UR Setup with the C30 section in Chapter 1 for details.
  • Page 94 Site List window will automatically be sent to the on-line communicating device. g) FIRMWARE UPGRADES The firmware of a C30 device can be upgraded, locally or remotely, via the EnerVista UR Setup software. The correspond- ing instructions are provided by the EnerVista UR Setup Help file under the topic “Upgrading Firmware”.
  • Page 95: Enervista Ur Setup Main Window

    Device data view windows, with common tool bar. Settings file data view windows, with common tool bar. Workspace area with data view tabs. Status bar. 10. Quick action hot links. 842786A2.CDR Figure 4–1: ENERVISTA UR SETUP SOFTWARE MAIN WINDOW GE Multilin C30 Controller System...
  • Page 96: Extended Enervista Ur Setup Features

    (settings file templates) and online devices (online settings templates). The func- tionality is identical for both purposes. The settings template feature requires that both the EnerVista UR Setup software and the C30 firmware are at ver- sions 5.40 or higher.
  • Page 97 The following procedure describes how to add password protection to a settings file template. Select a settings file from the offline window on the left of the EnerVista UR Setup main screen. Selecting the Template Mode > Password Protect Template option. GE Multilin C30 Controller System...
  • Page 98 Template Mode > View In Template Mode command. The template specifies that only the Pickup Curve Phase time overcurrent settings window without template applied. settings be available. 842858A1.CDR Figure 4–4: APPLYING TEMPLATES VIA THE VIEW IN TEMPLATE MODE COMMAND C30 Controller System GE Multilin...
  • Page 99 Select an installed device or settings file from the tree menu on the left of the EnerVista UR Setup main screen. Select the Template Mode > Remove Settings Template option. Enter the template password and click OK to continue. GE Multilin C30 Controller System...
  • Page 100: Securing And Locking Flexlogic™ Equations

    Click on Save to save and apply changes to the settings template. Select the Template Mode > View In Template Mode option to view the template. Apply a password to the template then click OK to secure the FlexLogic™ equation. C30 Controller System GE Multilin...
  • Page 101 FlexLogic™ entries in a settings file have been secured, use the following procedure to lock the settings file to a specific serial number. Select the settings file in the offline window. Right-click on the file and select the Edit Settings File Properties item. GE Multilin C30 Controller System...
  • Page 102: Settings File Traceability

    When a settings file is transfered to a C30 device, the date, time, and serial number of the C30 are sent back to EnerVista UR Setup and added to the settings file on the local PC. This infor- mation can be compared with the C30 actual values at any later date to determine if security has been compromised.
  • Page 103 4.2 EXTENDED ENERVISTA UR SETUP FEATURES The transfer date of a setting file written to a C30 is logged in the relay and can be viewed via EnerVista UR Setup or the front panel display. Likewise, the transfer date of a setting file saved to a local PC is logged in EnerVista UR Setup.
  • Page 104 ONLINE DEVICE TRACEABILITY INFORMATION The C30 serial number and file transfer date are available for an online device through the actual values. Select the Actual Values > Product Info > Model Information menu item within the EnerVista UR Setup online window as shown in the example below.
  • Page 105: Faceplate Interface

    LED panel 1 LED panel 2 LED panel 3 Display Front panel RS232 port Small user-programmable User-programmable Keypad (control) pushbuttons 1 to 7 pushbuttons 1 to 12 827801A7.CDR Figure 4–16: UR-SERIES STANDARD HORIZONTAL FACEPLATE PANELS GE Multilin C30 Controller System 4-13...
  • Page 106: Led Indicators

    The status indicators in the first column are described below. • IN SERVICE: This LED indicates that control power is applied, all monitored inputs, outputs, and internal systems are OK, and that the device has been programmed. 4-14 C30 Controller System GE Multilin...
  • Page 107 PHASE C: This LED indicates phase C was involved. • NEUTRAL/GROUND: This LED indicates that neutral or ground was involved. In the C30 Controller System, only the OTHER indicator is applicable and indicates that a digital element was involved. NOTE The user-programmable LEDs consist of 48 amber LED indicators in four columns.
  • Page 108 LED settings must be entered as shown in the User-programmable LEDs section of chapter 5. The LEDs are fully user-programmable. The default labels can be replaced by user-printed labels for both panels as explained in the following section. 4-16 C30 Controller System GE Multilin...
  • Page 109: Custom Labeling Of Leds

    Enter the text to appear next to each LED and above each user-programmable pushbuttons in the fields provided. Feed the C30 front panel label cutout sheet into a printer and press the Print button in the front panel report window.
  • Page 110 Bend the tabs at the left end of the tool upwards as shown below. Bend the tab at the center of the tool tail as shown below. The following procedure describes how to remove the LED labels from the C30 enhanced front panel and insert the custom labels.
  • Page 111 Slide the new LED label inside the pocket until the text is properly aligned with the LEDs, as shown below. The following procedure describes how to remove the user-programmable pushbutton labels from the C30 enhanced front panel and insert the custom labels.
  • Page 112 Slide the label tool under the user-programmable pushbutton label until the tabs snap out as shown below. This will attach the label tool to the user-programmable pushbutton label. Remove the tool and attached user-programmable pushbutton label as shown below. 4-20 C30 Controller System GE Multilin...
  • Page 113 The panel templates provide relative LED locations and located example text (x) edit boxes. The following procedure demonstrates how to install/uninstall the custom panel labeling. Remove the clear Lexan Front Cover (GE Multilin part number: 1501-0014). Push in...
  • Page 114: Display

    4.3.6 BREAKER CONTROL a) INTRODUCTION The C30 can interface with associated circuit breakers. In many cases the application monitors the state of the breaker, which can be presented on faceplate LEDs, along with a breaker trouble indication. Breaker operations can be manually initiated from faceplate keypad or automatically initiated from a FlexLogic™...
  • Page 115: Menus

    Each press of the MENU key advances through the following main heading pages: • Actual values. • Settings. • Commands. • Targets. • User displays (when enabled). GE Multilin C30 Controller System 4-23...
  • Page 116 FLASH MESSAGE Display Properties. TIME: 1.0 s To view the remaining settings associated with the Display Properties subheader, DEFAULT MESSAGE repeatedly press the MESSAGE DOWN key. The last message appears as shown. INTENSITY: 25% 4-24 C30 Controller System GE Multilin...
  • Page 117: Changing Settings

    ENTERING ALPHANUMERIC TEXT Text settings have data values which are fixed in length, but user-defined in character. They may be comprised of upper case letters, lower case letters, numerals, and a selection of special characters. GE Multilin C30 Controller System 4-25...
  • Page 118 When the "NEW SETTING HAS BEEN STORED" message appears, the relay will be in "Programmed" state and the In Service LED will turn on. e) ENTERING INITIAL PASSWORDS The C30 supports password entry from a local or remote connection. 4-26 C30 Controller System...
  • Page 119 In the event that an incorrect Command or Setting password has been entered via the faceplate interface three times within a three-minute time span, the FlexLogic™ operand will be set to “On” and the C30 will not allow LOCAL ACCESS DENIED Settings or Command access via the faceplate interface for the next ten minutes.
  • Page 120 FlexLogic™ operand will be set to “On” and REMOTE ACCESS DENIED the C30 will not allow Settings or Command access via the any external communications interface for the next ten minutes. FlexLogic™ operand will be set to “Off” after the expiration of the ten-minute timeout.
  • Page 121: Settings

    See page 5-47. DISPLAYS DIRECT I/O See page 5-49. TELEPROTECTION See page 5-57. INSTALLATION See page 5-57. SETTINGS BREAKERS See page 5-60. SYSTEM SETUP SWITCHES See page 5-64. SETTINGS FLEXLOGIC See page 5-78. FLEXLOGIC EQUATION EDITOR GE Multilin C30 Controller System...
  • Page 122: Virtual Inputs

    DNA BIT PAIRS REMOTE OUTPUTS See page 5-106. UserSt BIT PAIRS RESETTING See page 5-106. DIRECT INPUTS See page 5-107. DIRECT OUTPUTS See page 5-107. TELEPROTECTION See page 5-111. IEC 61850 See page 5-113. GOOSE ANALOGS C30 Controller System GE Multilin...
  • Page 123: Introduction To Elements

    The DPO event is created when the measure and decide comparator output transits from the pickup state (logic 1) to the dropout state (logic 0). This could happen when the element is in the operate state if the reset delay time is not ‘0’. GE Multilin C30 Controller System...
  • Page 124: Product Setup

    When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond- ing connection password. If the connection is to the back of the C30, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
  • Page 125 The remote password settings are only visible from a remote connection via the EnerVista UR Setup software. Select the Settings > Product Setup > Password Security menu item to open the remote password settings window. Figure 5–1: REMOTE PASSWORD SETTINGS WINDOW GE Multilin C30 Controller System...
  • Page 126 INVALID ATTEMPS BEFORE LOCKOUT The C30 provides a means to raise an alarm upon failed password entry. Should password verification fail while accessing a password-protected level of the relay (either settings or commands), the FlexLogic™ operand is UNAUTHORIZED ACCESS asserted.
  • Page 127: Clear Records

    When this timer expires, local setting access is ACCESS AUTH TIMEOUT immediately denied. If access is permitted and an off-to-on transition of the FlexLogic™ operand is detected, the time- out is restarted. The status of this timer is updated every 5 seconds. GE Multilin C30 Controller System...
  • Page 128: Display Properties

    DEFAULT MESSAGE TIMEOUT: If the keypad is inactive for a period of time, the relay automatically reverts to a default message. The inactivity time is modified via this setting to ensure messages remain on the screen long enough during programming or reading of actual values. C30 Controller System GE Multilin...
  • Page 129: Clear Relay Records

    Some customers prefer very low currents to display as zero, while others prefer the current be displayed even when the value reflects noise rather than the actual signal. The C30 applies a cut- off value to the magnitudes and angles of the measured currents.
  • Page 130: Communications

    MESSAGE HTTP PROTOCOL TFTP PROTOCOL See page 5–27. MESSAGE IEC 60870-5-104 See page 5–27. MESSAGE PROTOCOL SNTP PROTOCOL See page 5–28. MESSAGE EGD PROTOCOL MESSAGE See page 5–29. ETHERNET SWITCH See page 5–30. MESSAGE 5-10 C30 Controller System GE Multilin...
  • Page 131 0 ms The C30 is equipped with up to three independent serial communication ports. The faceplate RS232 port is intended for local use and is fixed at 19200 baud and no parity. The rear COM1 port type is selected when ordering: either an Ethernet or RS485 port.
  • Page 132 MODBUS SLAVE ADDRESS grammed. For the RS485 ports each C30 must have a unique address from 1 to 254. Address 0 is the broadcast address which all Modbus slave devices listen to. Addresses do not have to be sequential, but no two devices can have the same address or conflicts resulting in errors will occur.
  • Page 133 TIMEOUT: 120 s The C30 supports the Distributed Network Protocol (DNP) version 3.0. The C30 can be used as a DNP slave device con- nected to multiple DNP masters (usually an RTU or a SCADA master station). Since the C30 maintains two sets of DNP data change buffers and connection information, two DNP masters can actively communicate with the C30 at one time.
  • Page 134 DNP analog input points that are voltages will be returned with values 1000 times smaller (for example, a value of 72000 V on the C30 will be returned as 72). These settings are useful when analog input values must be adjusted to fit within cer- tain ranges in DNP masters.
  • Page 135 (for circuit breakers) or raise/lower (for tap changers) using a single control point. That is, the DNP master can operate a single point for both trip and close, or raise and lower, operations. The C30 can be configured to sup- port paired control points, with each paired control point operating two virtual inputs.
  • Page 136 IEC 60870-5-104 point lists must be in one continuous block, any points assigned after the first “Off” point NOTE are ignored. Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the C30 is restarted. NOTE 5-16...
  • Page 137 The C30 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supported over two protocol stacks: TCP/IP over ethernet and TP4/CLNP (OSI) over ethernet. The C30 operates as an IEC 61850 server. The Remote inputs and outputs section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.
  • Page 138 IEC 61850 GSSE application ID name string sent as part of each GSSE message. This GSSE ID string identifies the GSSE message to the receiving device. In C30 releases previous to 5.0x, this name string was repre- sented by the setting.
  • Page 139 DESTINATION MAC address; the least significant bit of the first byte must be set. In C30 releases previous to 5.0x, the destination Ethernet MAC address was determined automatically by taking the sending MAC address (that is, the unique, local MAC address of the C30) and setting the multicast bit.
  • Page 140 5 SETTINGS The C30 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station components.
  • Page 141 REMOTE IN 1 ITEM item to remote input 1. Remote input 1 can now be used in FlexLogic™ equations or other settings. The C30 must be rebooted (control power removed and re-applied) before these settings take effect. The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value in the sending device.
  • Page 142 CPU resources. When server scanning is disabled, there will be not updated to the IEC 61850 logical node sta- tus values in the C30. Clients will still be able to connect to the server (C30 relay), but most data values will not be updated.
  • Page 143 (_) character, and the first character in the prefix must be a letter. This conforms to the IEC 61850 standard. Changes to the logical node prefixes will not take effect until the C30 is restarted. The main menu for the IEC 61850 MMXU deadbands is shown below.
  • Page 144 The GGIO2 control configuration settings are used to set the control model for each input. The available choices are “0” (status only), “1” (direct control), and “2” (SBO with normal security). The GGIO2 control points are used to control the C30 virtual inputs.
  • Page 145 Changes to the report configuration will not take effect until the C30 is restarted. Please disconnect any IEC 61850 client connection to the C30 prior to making setting changes to the report config- uration. Disconnecting the rear Ethernet connection from the C30 will disconnect the IEC 61850 client connection.
  • Page 146 Since GSSE/GOOSE messages are multicast Ethernet by specification, they will not usually be forwarded by net- work routers. However, GOOSE messages may be fowarded by routers if the router has been configured for VLAN NOTE functionality. 5-26 C30 Controller System GE Multilin...
  • Page 147 NUMBER: The Trivial File Transfer Protocol (TFTP) can be used to transfer files from the C30 over a network. The C30 operates as a TFTP server. TFTP client software is available from various sources, including Microsoft Windows NT. The dir.txt file obtained from the C30 contains a list and description of all available files (event records, oscillography, etc.).
  • Page 148 C30 clock is closely synchronized with the SNTP/NTP server. It may take up to two minutes for the C30 to signal an SNTP self-test error if the server is offline.
  • Page 149 EXCH 1 DATA ITEM 20: MESSAGE (Modbus register address range) Fast exchanges (50 to 1000 ms) are generally used in control schemes. The C30 has one fast exchange (Exchange 1) and two slow exchanges (Exchanges 2 and 3). GE Multilin...
  • Page 150 EXCH 1 DATA ITEM 1 to 20/50: These settings specify the data items that are part of this EGD exchange. Almost any data from the C30 memory map can be configured to be included in an EGD exchange. The settings are the starting Modbus register address for the data item in decimal format.
  • Page 151: Modbus User Map

    “1”. An address value of “0” in the initial register means “none” and values of “0” will be dis- ADDRESS played for all registers. Different values can be entered as required in any of the register positions. ADDRESS GE Multilin C30 Controller System 5-31...
  • Page 152: Real Time Clock

    SNTP, the offset is used to determine the local time for the C30 clock, since SNTP provides UTC time. The daylight savings time (DST) settings can be used to allow the C30 clock can follow the DST rules of the local time zone.
  • Page 153: Oscillography

    Reducing the sampling rate allows longer records to be stored. This setting has no effect on the internal sampling rate of the relay which is always 64 samples per cycle; that is, it has no effect on the fundamental calculations of the device. GE Multilin C30 Controller System 5-33...
  • Page 154 IB signal on terminal 2 of the CT/VT module in slot F. If there are no CT/VT modules and analog input modules, no analog traces will appear in the file; only the digital traces will appear. 5-34 C30 Controller System GE Multilin...
  • Page 155: Data Logger

    DATA LOGGER MODE: This setting configures the mode in which the data logger will operate. When set to “Continu- ous”, the data logger will actively record any configured channels at the rate as defined by the . The DATA LOGGER RATE GE Multilin C30 Controller System 5-35...
  • Page 156: User-Programmable Leds

    All 62 LEDs on the relay are illuminated. This is a quick test to verify if any of the LEDs is “burned”. This stage lasts as long as the control input is on, up to a maximum of 1 minute. After 1 minute, the test will end. 5-36 C30 Controller System GE Multilin...
  • Page 157 Configure user-programmable pushbutton 1 by making the following entries in the SETTINGS menu: PRODUCT SETUP USER-PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1 “Self-reset” PUSHBUTTON 1 FUNCTION: “0.10 s” PUSHBTN 1 DROP-OUT TIME: GE Multilin C30 Controller System 5-37...
  • Page 158 “Latched”, the LED, once lit, remains so until reset by the faceplate RESET button, from a remote device via a com- munications channel, or from any programmed operand, even if the LED operand state de-asserts. 5-38 C30 Controller System GE Multilin...
  • Page 159: User-Programmable Self Tests

    Refer to the Relay self-tests section in chapter 7 for additional information on major and minor self-test alarms. To enable the Ethernet switch failure function, ensure that the is “Enabled” in this ETHERNET SWITCH FAIL FUNCTION menu. NOTE GE Multilin C30 Controller System 5-39...
  • Page 160: Control Pushbuttons

    The location of the control pushbuttons are shown in the following figures. Control pushbuttons 842813A1.CDR Figure 5–3: CONTROL PUSHBUTTONS (ENHANCED FACEPLATE) An additional four control pushbuttons are included on the standard faceplate when the C30 is ordered with the twelve user-programmable pushbutton option. STATUS EVENT CAUSE...
  • Page 161: User-Programmable Pushbuttons

    Range: 0 to 60.00 s in steps of 0.05 PUSHBTN 1 DROP-OUT MESSAGE TIME: 0.00 s Range: FlexLogic™ operand PUSHBTN 1 LED CTL: MESSAGE Range: Disabled, Normal, High Priority PUSHBTN 1 MESSAGE: MESSAGE Disabled Range: Disabled, Enabled PUSHBUTTON 1 MESSAGE EVENTS: Disabled GE Multilin C30 Controller System 5-41...
  • Page 162 The pushbutton is reset (deactivated) in latched mode by asserting the operand assigned to the set- PUSHBTN 1 RESET ting or by directly pressing the associated active front panel pushbutton. 5-42 C30 Controller System GE Multilin...
  • Page 163 This timer is reset upon release of the pushbutton. Note that any pushbutton operation will require the pushbutton to be pressed a minimum of 50 ms. This minimum time is required prior to activating the pushbutton hold timer. GE Multilin C30 Controller System 5-43...
  • Page 164 “Normal” if the setting is “High Priority” or “Normal”. PUSHBTN 1 MESSAGE • PUSHBUTTON 1 EVENTS: If this setting is enabled, each pushbutton state change will be logged as an event into event recorder. 5-44 C30 Controller System GE Multilin...
  • Page 165 Off = 0 SETTING SETTING Autoreset Delay Autoreset Function = Enabled = Disabled SETTING Drop-Out Timer TIMER FLEXLOGIC OPERAND 200 ms PUSHBUTTON 1 ON 842021A3.CDR Figure 5–8: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 1 of 2) GE Multilin C30 Controller System 5-45...
  • Page 166: Flex State Parameters

    16 states may be read out in a single Modbus register. The state bits can be configured so that all of the states which are of interest to the user are available in a minimum number of Modbus registers. 5-46 C30 Controller System GE Multilin...
  • Page 167: User-Definable Displays

    INVOKE AND SCROLL play, not at the first user-defined display. The pulses must last for at least 250 ms to take effect. INVOKE AND SCROLL GE Multilin C30 Controller System 5-47...
  • Page 168 4 seconds. While viewing a user display, press the ENTER key and then select the ‘Yes” option to remove the display from the user display list. Use the MENU key again to exit the user displays menu. 5-48 C30 Controller System GE Multilin...
  • Page 169: Direct Inputs And Outputs

    On type 7 cards that sup- port two channels, direct output messages are sent from both channels simultaneously. This effectively sends direct output GE Multilin C30 Controller System 5-49...
  • Page 170 Delivery time for direct input and output messages is approximately 0.2 of a power system cycle at 128 kbps and 0.4 of a power system cycle at 64 kbps, per each ‘bridge’. 5-50 C30 Controller System GE Multilin...
  • Page 171 The following application examples illustrate the basic concepts for direct input and output configuration. Please refer to the Inputs and outputs section in this chapter for information on configuring FlexLogic™ operands (flags, bits) to be exchanged. GE Multilin C30 Controller System 5-51...
  • Page 172 UR-series chassis. The problem is solved by adding an extra UR-series IED, such as the C30, to satisfy the additional input and output and programmable logic requirements. The two IEDs are connected via single-channel digital communication cards as shown in the figure below.
  • Page 173 The complete application requires addressing a number of issues such as failure of both the communications rings, failure or out-of-service conditions of one of the relays, etc. Self-monitoring flags of the direct inputs and outputs feature would be primarily used to address these concerns. GE Multilin C30 Controller System 5-53...
  • Page 174 Inputs and outputs section. A blocking pilot-aided scheme should be implemented with more security and, ideally, faster message delivery time. This could be accomplished using a dual-ring configuration as shown below. 5-54 C30 Controller System GE Multilin...
  • Page 175 EVENTS: Disabled The C30 checks integrity of the incoming direct input and output messages using a 32-bit CRC. The CRC alarm function is available for monitoring the communication medium noise by tracking the rate of messages failing the CRC check. The monitoring function counts all incoming messages, including messages that failed the CRC check.
  • Page 176 MESSAGE EVENTS: Disabled The C30 checks integrity of the direct input and output communication ring by counting unreturned messages. In the ring configuration, all messages originating at a given device should return within a pre-defined period of time. The unreturned messages alarm function is available for monitoring the integrity of the communication ring by tracking the rate of unre- turned messages.
  • Page 177: Teleprotection

    TERMINAL 1 ID NUMBER 5.2.17 INSTALLATION PATH: SETTINGS PRODUCT SETUP INSTALLATION Range: Not Programmed, Programmed INSTALLATION RELAY SETTINGS: Not Programmed Range: up to 20 alphanumeric characters RELAY NAME: MESSAGE Relay-1 GE Multilin C30 Controller System 5-57...
  • Page 178 This name will appear on generated reports. This name RELAY NAME is also used to identify specific devices which are engaged in automatically sending/receiving data over the Ethernet com- munications channel using the IEC 61850 protocol. 5-58 C30 Controller System GE Multilin...
  • Page 179: Remote Resources Configuration

    Bricks. Remote resources settings configure the point-to-point connection between specific fiber optic ports on the C30 process card and specific Brick. The relay is then configured to measure spe- cific currents, voltages and contact inputs from those Bricks, and to control specific outputs.
  • Page 180: Breakers

    Range: 0.000 to 1 000 000.000 s in steps of 0.001 MANUAL CLOSE RECAL1 MESSAGE TIME: 0.000 s Range: FlexLogic™ operand BREAKER 1 OUT OF SV: MESSAGE Range: Disabled, Enabled BREAKER 1 EVENTS: MESSAGE Disabled 5-60 C30 Controller System GE Multilin...
  • Page 181 1. The number of breaker control elements is dependent on the number of CT/VT modules specified with the C30. The follow- ing settings are available for each breaker control element.
  • Page 182 BREAKER 1 BLOCK CLOSE Off = 0 827061AS.CDR Figure 5–17: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 1 of 2) IEC 61850 functionality is permitted when the C30 is in “Programmed” mode and not in the local control mode. NOTE 5-62 C30 Controller System...
  • Page 183 FLEXLOGIC OPERANDS BREAKER 1 ANY P OPEN BREAKER 1 1P OPEN BREAKER 1 OOS SETTING BREAKER 1 OUT OF SV = Off 842025A1.CDR Figure 5–18: DUAL BREAKER CONTROL SCHEME LOGIC (Sheet 2 of 2) GE Multilin C30 Controller System 5-63...
  • Page 184: Disconnect Switches

    For greater security in determination of the switch pole position, both the 52/a and 52/b auxiliary contacts are used with reporting of the discrepancy between them. The number of available disconnect switches depends on the number of the CT/VT modules ordered with the C30. •...
  • Page 185 This allows for non-simultaneous operation of the poles. IEC 61850 functionality is permitted when the C30 is in “Programmed” mode and not in the local control mode. NOTE GE Multilin...
  • Page 186 FLEXLOGIC OPERANDS SWITCH Φ BAD ST SWITCH 1 C Φ CLSD SETTING SWITCH 1 C Φ OPEN SWITCH 1 ΦC OPENED SWITCH 1 C Φ INTERM = Off 842026A3.CDR Figure 5–19: DISCONNECT SWITCH SCHEME LOGIC 5-66 C30 Controller System GE Multilin...
  • Page 187: Introduction To Flexlogic™

    Figure 5–20: UR ARCHITECTURE OVERVIEW The states of all digital signals used in the C30 are represented by flags (or FlexLogic™ operands, which are described later in this section). A digital “1” is represented by a 'set' flag. Any external contact change-of-state can be used to block an element from operating, as an input to a control feature in a FlexLogic™...
  • Page 188 Some types of operands are present in the relay in multiple instances; e.g. contact and remote inputs. These types of oper- ands are grouped together (for presentation purposes only) on the faceplate display. The characteristics of the different types of operands are listed in the table below. Table 5–5: C30 FLEXLOGIC™ OPERAND TYPES OPERAND TYPE STATE...
  • Page 189 5 SETTINGS 5.5 FLEXLOGIC™ The operands available for this relay are listed alphabetically by types in the following table. Table 5–6: C30 FLEXLOGIC™ OPERANDS (Sheet 1 of 4) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION CONTROL CONTROL PUSHBTN 1 ON Control pushbutton 1 is being pressed...
  • Page 190 5.5 FLEXLOGIC™ 5 SETTINGS Table 5–6: C30 FLEXLOGIC™ OPERANDS (Sheet 2 of 4) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION ELEMENT: Dig Element 1 PKP Digital Element 1 is picked up Digital elements Dig Element 1 OP Digital Element 1 is operated...
  • Page 191 5 SETTINGS 5.5 FLEXLOGIC™ Table 5–6: C30 FLEXLOGIC™ OPERANDS (Sheet 3 of 4) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION FIXED OPERANDS Logic = 0. Does nothing and may be used as a delimiter in an equation list; used as ‘Disable’ by other features.
  • Page 192 5.5 FLEXLOGIC™ 5 SETTINGS Table 5–6: C30 FLEXLOGIC™ OPERANDS (Sheet 4 of 4) OPERAND TYPE OPERAND SYNTAX OPERAND DESCRIPTION REMOTE DEVICES REMOTE DEVICE 1 On Flag is set, logic=1 ↓ ↓ REMOTE DEVICE 16 On Flag is set, logic=1 REMOTE DEVICE 1 Off Flag is set, logic=1 ↓...
  • Page 193: Flexlogic™ Rules

    When making changes to settings, all FlexLogic™ equations are re-compiled whenever any new setting value is entered, so all latches are automatically reset. If it is necessary to re-initialize FlexLogic™ during testing, for example, it is suggested to power the unit down and then back up. GE Multilin C30 Controller System 5-73...
  • Page 194: Flexlogic™ Example

    DIGITAL ELEMENT 1 on Dropout State=Pickup (200 ms) DIGITAL ELEMENT 2 Timer 1 State=Operated Time Delay on Pickup (800 ms) CONTACT INPUT H1c State=Closed VIRTUAL OUTPUT 3 827026A2.VSD Figure 5–22: LOGIC EXAMPLE WITH VIRTUAL OUTPUTS 5-74 C30 Controller System GE Multilin...
  • Page 195 Following the procedure outlined, start with parameter 99, as follows: 99: The final output of the equation is virtual output 3, which is created by the operator "= Virt Op n". This parameter is therefore "= Virt Op 3." GE Multilin C30 Controller System 5-75...
  • Page 196 87: The input just below the upper input to OR #1 is operand “Virt Op 2 On". 86: The upper input to OR #1 is operand “Virt Op 1 On". 85: The last parameter is used to set the latch, and is operand “Virt Op 4 On". 5-76 C30 Controller System GE Multilin...
  • Page 197 In the following equation, virtual output 3 is used as an input to both latch 1 and timer 1 as arranged in the order shown below: DIG ELEM 2 OP Cont Ip H1c On AND(2) GE Multilin C30 Controller System 5-77...
  • Page 198: Flexlogic™ Equation Editor

    TIMER 1 TYPE: This setting is used to select the time measuring unit. • TIMER 1 PICKUP DELAY: Sets the time delay to pickup. If a pickup delay is not required, set this function to "0". 5-78 C30 Controller System GE Multilin...
  • Page 199: Flexelements™

    The element can be programmed to respond either to a signal level or to a rate-of-change (delta) over a pre-defined period of time. The output operand is asserted when the operating signal is higher than a threshold or lower than a threshold as per user's choice. GE Multilin C30 Controller System 5-79...
  • Page 200 The FLEXELEMENT 1 DIRECTION following figure explains the application of the FLEXELEMENT 1 DIRECTION FLEXELEMENT 1 PICKUP FLEXELEMENT 1 HYS- settings. TERESIS 5-80 C30 Controller System GE Multilin...
  • Page 201 FLEXELEMENT DIRECTION = Under; FLEXELEMENT INPUT MODE = Signed; FlexElement 1 OpSig FLEXELEMENT 1 PKP FLEXELEMENT DIRECTION = Under; FLEXELEMENT INPUT MODE = Absolute; FlexElement 1 OpSig 842706A2.CDR Figure 5–30: FLEXELEMENT™ INPUT MODE SETTING GE Multilin C30 Controller System 5-81...
  • Page 202 “Delta”. FLEXELEMENT 1 COMP MODE This setting specifies the pickup delay of the element. The setting FLEXELEMENT 1 PKP DELAY FLEXELEMENT 1 RST DELAY specifies the reset delay of the element. 5-82 C30 Controller System GE Multilin...
  • Page 203: Non-Volatile Latches

    FLEXLOGIC OPERANDS Off=0 LATCH 1 ON Dominant LATCH 1 OFF SETTING Previous Previous State State LATCH 1 SET: Off=0 RESET 842005A1.CDR Figure 5–31: NON-VOLATILE LATCH OPERATION TABLE (N = 1 to 16) AND LOGIC GE Multilin C30 Controller System 5-83...
  • Page 204: Overview

    Upon power-up, either the previous position is restored or the relay synchronizes to the current three-bit word (user set- ting). Basic alarm functionality alerts the user under abnormal conditions; for example, the three-bit control input being out of range. 5-84 C30 Controller System GE Multilin...
  • Page 205 The change is automatic and does not require explicit confirmation to change the selector position. When set to “Acknowledge”, the selector changes its posi- GE Multilin C30 Controller System 5-85...
  • Page 206 The selector position pre-selected via the stepping up control input has not been confirmed before the time out. SELECTOR 1 BIT ALARM The selector position pre-selected via the three-bit control input has not been confirmed before the time out. 5-86 C30 Controller System GE Multilin...
  • Page 207 3BIT A1 3BIT A2 POS 1 POS 2 POS 3 POS 4 POS 5 POS 6 POS 7 BIT 0 BIT 1 BIT 2 STP ALARM BIT ALARM ALARM 842737A1.CDR Figure 5–32: TIME-OUT MODE GE Multilin C30 Controller System 5-87...
  • Page 208 GROUP 3 ACTIVATE ON: Make the following changes to selector switch element in the SETTINGS CONTROL ELEMENTS SELECTOR SWITCH menu to assign control to user programmable pushbutton 1 and contact inputs 1 through 3: SELECTOR SWITCH 1 5-88 C30 Controller System GE Multilin...
  • Page 209 3-bit acknowledge SELECTOR 1 BIT ALARM 3-bit position out SELECTOR 1 ALARM SELECTOR 1 PWR ALARM SELECTOR 1 BIT 0 SELECTOR 1 BIT 1 SELECTOR 1 BIT 2 842012A2.CDR Figure 5–34: SELECTOR SWITCH LOGIC GE Multilin C30 Controller System 5-89...
  • Page 210: Digital Elements

    Some versions of the digital input modules include an active voltage monitor circuit connected across form-A contacts. The voltage monitor circuit limits the trickle current through the output circuit (see technical specifications for form-A). 5-90 C30 Controller System GE Multilin...
  • Page 211 The settings to use digital element 1 to monitor the breaker trip circuit are indicated below (EnerVista UR Setup example shown): setting should be greater than the operating time of the breaker to avoid nuisance PICKUP DELAY alarms. NOTE GE Multilin C30 Controller System 5-91...
  • Page 212 V = voltage monitor 827074A3.CDR Figure 5–37: TRIP CIRCUIT EXAMPLE 2 The wiring connection for two examples above is applicable to both form-A contacts with voltage monitoring and solid-state contact with voltage monitoring. NOTE 5-92 C30 Controller System GE Multilin...
  • Page 213: Digital Counters

    –2,147,483,648 counts, the counter will rollover to +2,147,483,647. • COUNTER 1 BLOCK: Selects the FlexLogic™ operand for blocking the counting operation. All counter operands are blocked. GE Multilin C30 Controller System 5-93...
  • Page 214 COUNTER 1 RESET: COUNTER 1 FROZEN: Off = 0 STORE DATE & TIME Date & Time SETTING COUNT1 FREEZE/RESET: Off = 0 827065A1.VSD SETTING COUNT1 FREEZE/COUNT: Off = 0 Figure 5–38: DIGITAL COUNTER SCHEME LOGIC 5-94 C30 Controller System GE Multilin...
  • Page 215: Bit Switches

    If the control operand is in the "Off" state, the first (A) input is switched to the output. If the control oper- and is in the "On" state, the second (B) input is switched to the output. The switching takes place instantaneously. GE Multilin C30 Controller System 5-95...
  • Page 216 FLEXLOG C OPE AND Off = 0 8BIT SW 1 ARG B7: 8BIT SWITCH 1 BIT 7 Off = 0 ETT NG 8BIT SW 1 CONTROL: Off = 0 842017A1.CDR Figure 5–39: 8-BIT SWITCH LOGIC 5-96 C30 Controller System GE Multilin...
  • Page 217: Contact Inputs

    The DC input voltage is compared to a user-settable threshold. A new contact input state must be maintained for a user- settable debounce time in order for the C30 to validate the new contact state. In the figure below, the debounce time is set at 2.5 ms;...
  • Page 218 Event Records menu, make the following settings changes: "Breaker Closed (52b)" CONTACT INPUT H5A ID: "Enabled" CONTACT INPUT H5A EVENTS: Note that the 52b contact is closed when the breaker is open and open when the breaker is closed. 5-98 C30 Controller System GE Multilin...
  • Page 219: Virtual Inputs

    “Virtual Input 1 to ON = 1” “Virtual Input 1 to OFF = 0” VIRTUAL INPUT 1 ID: (Flexlogic Operand) Virt Ip 1 VIRTUAL INPUT 1 TYPE: Latched Self - Reset 827080A2.CDR Figure 5–41: VIRTUAL INPUTS SCHEME LOGIC GE Multilin C30 Controller System 5-99...
  • Page 220: Contact Outputs

    The most dependable protection of the initiating contact is provided by directly measuring current in the tripping circuit, and using this parameter to control resetting of the initiating relay. This scheme is often called trip seal-in. This can be realized in the C30 using the FlexLogic™ operand to seal-in the contact output as follows: CONT OP 1 ION “Cont Op 1"...
  • Page 221 5.7 INPUTS/OUTPUTS The C30 latching output contacts are mechanically bi-stable and controlled by two separate (open and close) coils. As such they retain their position even if the relay is not powered up. The relay recognizes all latching output contact cards and pop- ulates the setting menu accordingly.
  • Page 222: Virtual Outputs

    FlexLogic™ equations. Any change of state of a virtual output can be logged as an event if programmed to do so. For example, if Virtual Output 1 is the trip signal from FlexLogic™ and the trip relay is used to signal events, the settings would be programmed as follows: 5-102 C30 Controller System GE Multilin...
  • Page 223: Remote Devices

    The remote input/output facility provides for 64 remote inputs and 64 remote outputs. b) LOCAL DEVICES: ID OF DEVICE FOR TRANSMITTING GSSE MESSAGES In a C30 relay, the device ID that represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each GOOSE message is programmed in the...
  • Page 224: Remote Inputs

    This setting identifies the Ethernet application identification in the GOOSE message. It should match the corre- sponding settings on the sending device. setting provides for the choice of the C30 fixed (DNA/UserSt) dataset (that is, containing REMOTE DEVICE 1 DATASET DNA and UserSt bit pairs), or one of the configurable datasets.
  • Page 225: Remote Double-Point Status Inputs

    PATH: SETTINGS INPUTS/OUTPUTS REMOTE OUTPUTS DNA BIT PAIRS REMOTE OUPUTS DNA- 1(32) BIT PAIR Range: FlexLogic™ operand REMOTE OUTPUTS DNA- 1 OPERAND: DNA- 1 BIT PAIR Range: Disabled, Enabled DNA- 1 EVENTS: MESSAGE Disabled GE Multilin C30 Controller System 5-105...
  • Page 226: Resetting

    FlexLogic™ operand. Each individual source of a RESET command also creates its individual operand RESET OP to identify the source of the command. The setting RESET OP (PUSHBUTTON) RESET OP (COMMS) RESET OP (OPERAND) shown above selects the operand that will create the operand. RESET OP (OPERAND) 5-106 C30 Controller System GE Multilin...
  • Page 227: Direct Inputs/Outputs

    FlexLogic™ operand that determines the state of this direct output. c) APPLICATION EXAMPLES The examples introduced in the earlier Direct inputs and outputs section (part of the Product Setup section) are continued below to illustrate usage of the direct inputs and outputs. GE Multilin C30 Controller System 5-107...
  • Page 228 UR-series chassis. The problem is solved by adding an extra UR-series IED, such as the C30, to satisfy the additional inputs/outputs and programmable logic requirements. The two IEDs are connected via single-channel digital communication cards as shown below.
  • Page 229 "3" (effectively, this is a message from IED 1) DIRECT INPUT 6 BIT NUMBER: UR IED 2: "1" DIRECT INPUT 5 DEVICE ID: "2" DIRECT INPUT 5 BIT NUMBER: "3" DIRECT INPUT 6 DEVICE ID: "2" DIRECT INPUT 6 BIT NUMBER: GE Multilin C30 Controller System 5-109...
  • Page 230 In three-terminal applications, both the remote terminals must grant permission to trip. Therefore, at each terminal, direct inputs 5 and 6 should be ANDed in FlexLogic™ and the resulting operand configured as the permission to trip ( HYB POTT setting). 5-110 C30 Controller System GE Multilin...
  • Page 231: Teleprotection Inputs And Outputs

    The “Latest/On” and “Latest/Off” values freeze the input in case of lost communications. If the latest state is not known, such as after relay power-up but before the first communication exchange, then the input defaults to logic 1 for “Latest/On” and logic 0 for “Latest/Off”. GE Multilin C30 Controller System 5-111...
  • Page 232 (On 3-terminal system or 2-terminal (same for 1-2...1-16) SETTING with redundant channel) FLEXLOGIC OPERAND TELEPROT OUTPUT 2-1: (same for 2-2...2-16) Fail TELEPRO INPUT 2-1 On Off (Flexlogic Operand) (same for 1-2...1-16) 842750A2.CDR Figure 5–47: TELEPROTECTION INPUT/OUTPUT PROCESSING 5-112 C30 Controller System GE Multilin...
  • Page 233: Iec 61850 Goose Analogs

    GOOSE ANALOG 1 PU: This setting specifies the per-unit base factor when using the GOOSE analog input FlexAna- log™ values in other C30 features, such as FlexElements™. The base factor is applied to the GOOSE analog input FlexAnalog quantity to normalize it to a per-unit quantity. The base units are described in the following table.
  • Page 234: Dcma Inputs

    –20 to +180 MW; in this case the value would be “–20” and the DCMA INPUT F1 MIN VALUE DCMA INPUT F1 MAX value “180”. Intermediate values between the min and max values are scaled linearly. VALUE 5-114 C30 Controller System GE Multilin...
  • Page 235: Rtd Inputs

    1.5 pu. FlexElement™ operands are available to FlexLogic™ for further interlocking or to operate an output contact directly. Refer to the following table for reference temperature values for each RTD type. GE Multilin C30 Controller System 5-115...
  • Page 236 224.92 15.61 168.47 280.77 233.97 16.00 172.46 291.96 243.30 16.39 175.84 303.46 252.88 16.78 179.51 315.31 262.76 17.17 183.17 327.54 272.94 17.56 186.82 340.14 283.45 17.95 190.45 353.14 294.28 18.34 194.08 366.53 305.44 18.73 5-116 C30 Controller System GE Multilin...
  • Page 237: Dcma Outputs

    – MAX VAL MIN VAL MAX VAL < 0.1 pu. The resulting characteristic is illustrated in the following figure. DRIVING SIGNAL MIN VAL MAX VAL 842739A1.CDR Figure 5–48: DCMA OUTPUT CHARACTERISTIC GE Multilin C30 Controller System 5-117...
  • Page 238 (i.e. if DCMA OUTPUT F1 MIN VAL DCMA OUTPUT F1 MAX VAL is set to FlexAnalog value based on power factor measurement). DCMA OUTPUT F1 SOURCE NOTE 5-118 C30 Controller System GE Multilin...
  • Page 239: Test Mode

    TEST MODE FORCING: MESSAGE The C30 provides a test facility to verify the functionality of contact inputs and outputs, some communication channels and the phasor measurement unit (where applicable), using simulated conditions. The test mode is indicated on the relay face- plate by a Test Mode LED indicator.
  • Page 240: Force Contact Inputs

    Following a restart, power up, settings TEST MODE FUNCTION upload, or firmware upgrade, the test mode will remain at the last programmed value. This allows a C30 that has been placed in isolated mode to remain isolated during testing and maintenance activities. On restart, the TEST MODE FORCING setting and the force contact input and force contact output settings all revert to their default states.
  • Page 241: Force Contact Outputs

    USER PUSHBUTTON 1 PUSHBUTTON 1 FUNCTION input 1 to initiate the Test mode, make the following changes in the menu: SETTINGS TESTING TEST MODE “Enabled” and “ ” TEST MODE FUNCTION: TEST MODE INITIATE: GE Multilin C30 Controller System 5-121...
  • Page 242 5.9 TESTING 5 SETTINGS 5-122 C30 Controller System GE Multilin...
  • Page 243: Actual Values Main Menu

    See page 6-8. STATUS TELEPROT CH TESTS See page 6-8. ETHERNET SWITCH See page 6-9. ACTUAL VALUES FLEXELEMENTS See page 6-10. METERING IEC 61850 See page 6-10. GOOSE ANALOGS TRANSDUCER I/O See page 6-10. DCMA INPUTS GE Multilin C30 Controller System...
  • Page 244 See page 6-10. RTD INPUTS ACTUAL VALUES EVENT RECORDS See page 6-11. RECORDS OSCILLOGRAPHY See page 6-11. DATA LOGGER See page 6-12. ACTUAL VALUES MODEL INFORMATION See page 6-13. PRODUCT INFO FIRMWARE REVISIONS See page 6-13. C30 Controller System GE Multilin...
  • Page 245: Contact Inputs

    The state displayed will be that of the remote point unless the remote device has been established to be “Offline” in which case the value shown is the programmed default state for the remote input. GE Multilin C30 Controller System...
  • Page 246: Remote Double-Point Status Inputs

    The present state of the contact outputs is shown here. The first line of a message display indicates the ID of the contact output. For example, ‘Cont Op 1’ refers to the contact output in terms of the default name-array index. The second line of the display indicates the logic state of the contact output. C30 Controller System GE Multilin...
  • Page 247: Virtual Outputs

    DNA or UserSt bit occurs. The SqNum number is obtained from the indicated remote device and is incremented whenever a GSSE message is sent. This number will rollover to zero when a count of 4 294 967 295 is incremented. GE Multilin C30 Controller System...
  • Page 248: Selector Switches

    PATH: ACTUAL VALUES STATUS ETHERNET Range: Fail, OK ETHERNET ETHERNET PRI LINK STATUS: OK Range: Fail, OK ETHERNET SEC LINK MESSAGE STATUS: OK These values indicate the status of the primary and secondary Ethernet links. C30 Controller System GE Multilin...
  • Page 249: Direct Inputs

    DIRECT DEVICE 1 STATUS STATUS: Offline Range: Offline, Online DIRECT DEVICE 2 MESSAGE STATUS: Offline ↓ Range: Offline, Online DIRECT DEVICE 16 MESSAGE STATUS: Offline These actual values represent the state of direct devices 1 through 16. GE Multilin C30 Controller System...
  • Page 250: Egd Protocol Status

    “FAIL” message will be displayed. The “N/A” value appears if the local relay ID is set to a default value of “0”, the chan- nel is failed, or if the teleprotection inputs/outputs are not enabled. C30 Controller System GE Multilin...
  • Page 251 SWITCH MAC ADDRESS: MESSAGE 00A0F40138FA These actual values appear only if the C30 is ordered with an Ethernet switch module (type 2S or 2T). The status informa- tion for the Ethernet switch is shown in this menu. • SWITCH 1 PORT STATUS to SWITCH 6 PORT STATUS: These values represents the receiver status of each port on the Ethernet switch.
  • Page 252: Flexelements™

    MESSAGE 0.000 The C30 Controller System is provided with optional IEC 61850 communications capability. This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chapter 2 for addi- tional details. The IEC 61850 protocol features are not available if CPU type E is ordered.
  • Page 253 5 for additional details. A trigger can be forced here at any time by setting “Yes” to the command. Refer to the FORCE TRIGGER? COMMANDS menu for information on clearing the oscillography records. CLEAR RECORDS GE Multilin C30 Controller System 6-11...
  • Page 254 It counts up at the defined sampling rate. If the data logger channels are defined, then both values are static. Refer to the menu for clearing data logger records. COMMANDS CLEAR RECORDS 6-12 C30 Controller System GE Multilin...
  • Page 255 6.5 PRODUCT INFORMATION 6.5PRODUCT INFORMATION 6.5.1 MODEL INFORMATION PATH: ACTUAL VALUES PRODUCT INFO MODEL INFORMATION Range: standard GE multilin order code format; MODEL INFORMATION ORDER CODE LINE 1: example order code shown C30-E00-HCH-F6A-H6A Range: standard GE multilin order code format...
  • Page 256 6.5 PRODUCT INFORMATION 6 ACTUAL VALUES 6-14 C30 Controller System GE Multilin...
  • Page 257 The states of up to 64 virtual inputs are changed here. The first line of the display indicates the ID of the virtual input. The second line indicates the current or selected status of the virtual input. This status will be a state off (logic 0) or on (logic 1). GE Multilin C30 Controller System...
  • Page 258: Relay Maintenance

    If an update occurs, the following message is shown. UPDATING... PLEASE WAIT There is no impact if there have been no changes to the hardware modules. When an update does not occur, the ORDER message will be shown. CODE NOT UPDATED C30 Controller System GE Multilin...
  • Page 259: Targets Menu

    The critical fail relay on the power supply module is de-energized. • All other output relays are de-energized and are prevented from further operation. • The faceplate In Service LED indicator is turned off. • event is recorded. RELAY OUT OF SERVICE GE Multilin C30 Controller System...
  • Page 260 Contact Factory (xxx) • Latched target message: Yes. • Description of problem: One or more installed hardware modules is not compatible with the C30 order code. • How often the test is performed: Module dependent. • What to do: Contact the factory and supply the failure code noted in the display. The “xxx” text identifies the failed mod- ule (for example, F8L).
  • Page 261 How often the test is performed: Monitored every five seconds. An error is issued after five consecutive failures • What to do: Check the C30 device and switch IP configuration settings. Check for incorrect UR port (port 7) settings on the Ethernet switch. Check the power to the switch.
  • Page 262 • What to do: Check direct input and output configuration and wiring. REMOTE DEVICE FAIL: COMM Path Incomplete • Latched target message: No. • Description of problem: One or more GOOSE devices are not responding. C30 Controller System GE Multilin...
  • Page 263 • Latched target message: Yes. • Description of problem: Abnormal restart from modules being removed or inserted while the C30 is powered-up, when there is an abnormal DC supply, or as a result of internal relay failure. • How often the test is performed: Event driven.
  • Page 264 7.2 TARGETS 7 COMMANDS AND TARGETS C30 Controller System GE Multilin...
  • Page 265: Parameter List

    RTD input 18 actual value 13570 RTD Inputs 19 Value RTD input 19 actual value 13571 RTD Inputs 20 Value RTD input 20 actual value 13572 RTD Inputs 21 Value RTD input 21 actual value GE Multilin C30 Controller System...
  • Page 266 IEC 61850 GOOSE analog input 7 45598 GOOSE Analog In 8 IEC 61850 GOOSE analog input 8 45600 GOOSE Analog In 9 IEC 61850 GOOSE analog input 9 45602 GOOSE Analog In 10 IEC 61850 GOOSE analog input 10 C30 Controller System GE Multilin...
  • Page 267 IEC 61850 GOOSE analog input 13 45610 GOOSE Analog In 14 IEC 61850 GOOSE analog input 14 45612 GOOSE Analog In 15 IEC 61850 GOOSE analog input 15 45614 GOOSE Analog In 16 IEC 61850 GOOSE analog input 16 GE Multilin C30 Controller System...
  • Page 268 A.1 PARAMETER LIST APPENDIX A C30 Controller System GE Multilin...
  • Page 269: Introduction

    Broadcast mode is only recognized when associated with function code 05h. For any other function code, a packet with broadcast mode slave address 0 will be ignored. GE Multilin C30 Controller System...
  • Page 270: Algorithm

    No: go to 8; Yes: G (+) A --> A and continue. Is j = 8? No: go to 5; Yes: continue i + 1 --> i Is i = N? No: go to 3; Yes: continue A --> CRC C30 Controller System GE Multilin...
  • Page 271: Modbus Function Codes

    125. See the Modbus memory map table for exact details on the data registers. Since some PLC implementations of Modbus only support one of function codes 03h and 04h. The C30 interpretation allows either function code to be used for reading one or more consecutive data registers.
  • Page 272: Execute Operation (Function Code 05H

    DATA STARTING ADDRESS - high DATA STARTING ADDRESS - low DATA STARTING ADDRESS - low DATA - high DATA - high DATA - low DATA - low CRC - low CRC - low CRC - high CRC - high C30 Controller System GE Multilin...
  • Page 273: Store Multiple Settings (Function Code 10H

    EXAMPLE (HEX) PACKET FORMAT EXAMPLE (HEX) SLAVE ADDRESS SLAVE ADDRESS FUNCTION CODE FUNCTION CODE CRC - low order byte ERROR CODE CRC - high order byte CRC - low order byte CRC - high order byte GE Multilin C30 Controller System...
  • Page 274: File Transfers

    Cleared Date to the present date and time. To read binary COMTRADE oscillography files, read the following filenames: OSCnnnn.CFG and OSCnnn.DAT Replace “nnn” with the desired oscillography trigger number. For ASCII format, use the following file names OSCAnnnn.CFG and OSCAnnn.DAT C30 Controller System GE Multilin...
  • Page 275: Modbus Password Operation

    When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond- ing connection password. If the connection is to the back of the C30, the remote password must be used. If the connection is to the RS232 port of the faceplate, the local password must be used.
  • Page 276: Memory Mapping

    0 (Off) 0419 Virtual Input 26 State 0 to 1 F108 0 (Off) 041A Virtual Input 27 State 0 to 1 F108 0 (Off) 041B Virtual Input 28 State 0 to 1 F108 0 (Off) C30 Controller System GE Multilin...
  • Page 277 ...Repeated for Digital Counter 7 0838 ...Repeated for Digital Counter 8 FlexStates (Read Only) 0900 FlexState Bits (16 items) 0 to 65535 F001 Element States (Read Only) 1000 Element Operate States (64 items) 0 to 65535 F502 GE Multilin C30 Controller System...
  • Page 278 1 to 64 F205 "Rem Ip 1" 2610 Remote double-point status input 1 input state (read only) 0 to 3 F605 3 (Bad) 2611 Remote double-point status input 1 events 0 to 1 F102 0 (Disabled) B-10 C30 Controller System GE Multilin...
  • Page 279 DCMA Inputs 17 Value -9999999 to 9999999 F004 34E2 DCMA Inputs 18 Value -9999999 to 9999999 F004 34E4 DCMA Inputs 19 Value -9999999 to 9999999 F004 34E6 DCMA Inputs 20 Value -9999999 to 9999999 F004 GE Multilin C30 Controller System B-11...
  • Page 280 -32768 to 32767 °C F002 351D RTD Input 46 Value -32768 to 32767 °C F002 351E RTD Input 47 Value -32768 to 32767 °C F002 351F RTD Input 48 Value -32768 to 32767 °C F002 B-12 C30 Controller System GE Multilin...
  • Page 281 DNP Address 0 to 65519 F001 409D Reserved 0 to 1 F001 409E DNP Client Addresses (2 items) 0 to 4294967295 F003 40A3 TCP Port Number for the Modbus protocol 1 to 65535 F001 GE Multilin C30 Controller System B-13...
  • Page 282 Ethernet switch Modbus IP port number 1 to 65535 F001 414B Ethernet switch Port 1 Events 0 to 1 F102 0 (Disabled) 414C Ethernet switch Port 2 Events 0 to 1 F102 0 (Disabled) B-14 C30 Controller System GE Multilin...
  • Page 283 Trip LED Input FlexLogic Operand 0 to 65535 F300 4261 Alarm LED Input FlexLogic Operand 0 to 65535 F300 User Programmable LEDs (Read/Write Setting) (48 modules) 4280 FlexLogic™ Operand to Activate LED 0 to 65535 F300 GE Multilin C30 Controller System B-15...
  • Page 284 F202 “Relay-1” User Programmable Self Tests (Read/Write Setting) 4441 User Programmable Detect Ring Break Function 0 to 1 F102 1 (Enabled) 4442 User Programmable Direct Device Off Function 0 to 1 F102 1 (Enabled) B-16 C30 Controller System GE Multilin...
  • Page 285 ...Repeated for User-Definable Display 14 4DC0 ...Repeated for User-Definable Display 15 4DE0 ...Repeated for User-Definable Display 16 User Programmable Pushbuttons (Read/Write Setting) (12 modules) 4E00 User Programmable Pushbutton 1 Function 0 to 2 F109 2 (Disabled) GE Multilin C30 Controller System B-17...
  • Page 286 ...Repeated for RTD Input 19 5569 ...Repeated for RTD Input 20 557C ...Repeated for RTD Input 21 558F ...Repeated for RTD Input 22 55A2 ...Repeated for RTD Input 23 55B5 ...Repeated for RTD Input 24 B-18 C30 Controller System GE Multilin...
  • Page 287 ...Repeated for FlexLogic™ Timer 21 58A8 ...Repeated for FlexLogic™ Timer 22 58B0 ...Repeated for FlexLogic™ Timer 23 58B8 ...Repeated for FlexLogic™ Timer 24 58C0 ...Repeated for FlexLogic™ Timer 25 58C8 ...Repeated for FlexLogic™ Timer 26 GE Multilin C30 Controller System B-19...
  • Page 288 F300 754E Disconnect switch 1 phase C opened 0 to 65535 F300 754F Disconnect switch 1 operate time 0 to 2 0.001 F001 7550 Disconnect switch 1 alarm delay 0 to 1000000 0.001 F003 B-20 C30 Controller System GE Multilin...
  • Page 289 ...Repeated for Switch 3 8348 ...Repeated for Switch 4 8360 ...Repeated for Switch 5 8378 ...Repeated for Switch 6 EGD Fast Production Status (Read Only) 83E0 EGD Fast Producer Exchange 1 Signature 0 to 65535 F001 GE Multilin C30 Controller System B-21...
  • Page 290 ...Repeated for Digital Element 17 8B54 ...Repeated for Digital Element 18 8B68 ...Repeated for Digital Element 19 8B7C ...Repeated for Digital Element 20 8B90 ...Repeated for Digital Element 21 8BA4 ...Repeated for Digital Element 22 B-22 C30 Controller System GE Multilin...
  • Page 291 0 to 2 F109 0 (Self-reset) 8E16 Trip Bus 1 Events 0 to 1 F102 0 (Disabled) 8E18 Reserved (8 items) F001 8E20 ...Repeated for Trip Bus 2 8E40 ...Repeated for Trip Bus 3 GE Multilin C30 Controller System B-23...
  • Page 292 ...Repeated for dcmA Output 10 933C ...Repeated for dcmA Output 11 9342 ...Repeated for dcmA Output 12 9348 ...Repeated for dcmA Output 13 934E ...Repeated for dcmA Output 14 9354 ...Repeated for dcmA Output 15 B-24 C30 Controller System GE Multilin...
  • Page 293 -2147483.647 to 2147483.647 0.001 F004 9A0D FlexElement™ 7 Actual -2147483.647 to 2147483.647 0.001 F004 9A0F FlexElement™ 8 Actual -2147483.647 to 2147483.647 0.001 F004 Teleprotection Inputs/Outputs (Read/Write Settings) 9B00 Teleprotection Function 0 to 1 F102 0 (Disabled) GE Multilin C30 Controller System B-25...
  • Page 294 F300 A704 Non-Volatile Latch 1 Target 0 to 2 F109 0 (Self-reset) A705 Non-Volatile Latch 1 Events 0 to 1 F102 0 (Disabled) A706 Reserved (4 items) F001 A70A ...Repeated for Non-Volatile Latch 2 B-26 C30 Controller System GE Multilin...
  • Page 295 ...Repeated for IEC 61850 GOOSE analog input 11 AA4D ...Repeated for IEC 61850 GOOSE analog input 12 AA54 ...Repeated for IEC 61850 GOOSE analog input 13 AA5B ...Repeated for IEC 61850 GOOSE analog input 14 GE Multilin C30 Controller System B-27...
  • Page 296 0 to 65534 F206 (none) ADDF IEC 61850 logical node CSWIx name prefix (6 items) 0 to 65534 F206 (none) AE39 IEC 61850 logical node XSWIx name prefix (6 items) 0 to 65534 F206 (none) B-28 C30 Controller System GE Multilin...
  • Page 297 ...Repeated for IEC 61850 GGIO4 analog input 18 AF8E ...Repeated for IEC 61850 GGIO4 analog input 19 AF95 ...Repeated for IEC 61850 GGIO4 analog input 20 AF9C ...Repeated for IEC 61850 GGIO4 analog input 21 GE Multilin C30 Controller System B-29...
  • Page 298 IEC 61850 MMXU VA.phsB Deadband 1 0.001 to 100 0.001 F003 10000 B0EE IEC 61850 MMXU VA.phsC Deadband 1 0.001 to 100 0.001 F003 10000 B0F0 IEC 61850 MMXU PF.phsA Deadband 1 0.001 to 100 0.001 F003 10000 B-30 C30 Controller System GE Multilin...
  • Page 299 IEC 61850 GGIO2.CF.SPCSO43.ctlModel Value 0 to 2 F001 B26B IEC 61850 GGIO2.CF.SPCSO44.ctlModel Value 0 to 2 F001 B26C IEC 61850 GGIO2.CF.SPCSO45.ctlModel Value 0 to 2 F001 B26D IEC 61850 GGIO2.CF.SPCSO46.ctlModel Value 0 to 2 F001 GE Multilin C30 Controller System B-31...
  • Page 300 F003 B5CA Configurable GOOSE Dataset Items for Transmission 0 to 256 F232 0 (None) B60A ...Repeated for Module 2 B674 ...Repeated for Module 3 B6DE ...Repeated for Module 4 B748 ...Repeated for Module 5 B-32 C30 Controller System GE Multilin...
  • Page 301 ...Repeated for Contact Input 34 BC10 ...Repeated for Contact Input 35 BC18 ...Repeated for Contact Input 36 BC20 ...Repeated for Contact Input 37 BC28 ...Repeated for Contact Input 38 BC30 ...Repeated for Contact Input 39 GE Multilin C30 Controller System B-33...
  • Page 302 ...Repeated for Contact Input 88 BDC0 ...Repeated for Contact Input 89 BDC8 ...Repeated for Contact Input 90 BDD0 ...Repeated for Contact Input 91 BDD8 ...Repeated for Contact Input 92 BDE0 ...Repeated for Contact Input 93 B-34 C30 Controller System GE Multilin...
  • Page 303 ...Repeated for Virtual Input 39 C004 ...Repeated for Virtual Input 40 C010 ...Repeated for Virtual Input 41 C01C ...Repeated for Virtual Input 42 C028 ...Repeated for Virtual Input 43 C034 ...Repeated for Virtual Input 44 GE Multilin C30 Controller System B-35...
  • Page 304 ...Repeated for Virtual Output 26 C200 ...Repeated for Virtual Output 27 C208 ...Repeated for Virtual Output 28 C210 ...Repeated for Virtual Output 29 C218 ...Repeated for Virtual Output 30 C220 ...Repeated for Virtual Output 31 B-36 C30 Controller System GE Multilin...
  • Page 305 ...Repeated for Virtual Output 80 C3B0 ...Repeated for Virtual Output 81 C3B8 ...Repeated for Virtual Output 82 C3C0 ...Repeated for Virtual Output 83 C3C8 ...Repeated for Virtual Output 84 C3D0 ...Repeated for Virtual Output 85 GE Multilin C30 Controller System B-37...
  • Page 306 ...Repeated for Contact Output 25 C56C ...Repeated for Contact Output 26 C578 ...Repeated for Contact Output 27 C584 ...Repeated for Contact Output 28 C590 ...Repeated for Contact Output 29 C59C ...Repeated for Contact Output 30 B-38 C30 Controller System GE Multilin...
  • Page 307 Clear Platform Direct Input/Output Statistics operand 0 to 65535 F300 C782 Reserved (13 items) F001 Force Contact Inputs/Outputs (Read/Write Settings) C7A0 Force Contact Input x State (96 items) 0 to 2 F144 0 (Disabled) GE Multilin C30 Controller System B-39...
  • Page 308 ...Repeated for Direct Output 2 CA14 ...Repeated for Direct Output 3 CA16 ...Repeated for Direct Output 4 CA18 ...Repeated for Direct Output 5 CA1A ...Repeated for Direct Output 6 CA1C ...Repeated for Direct Output 7 B-40 C30 Controller System GE Multilin...
  • Page 309 0 to 16383 F001 CB22 Remote Device 1 GOOSE Dataset 0 to 8 F184 0 (Fixed) CB23 ...Repeated for Device 2 CB46 ...Repeated for Device 3 CB69 ...Repeated for Device 4 CB8C ...Repeated for Device 5 GE Multilin C30 Controller System B-41...
  • Page 310 ...Repeated for Remote Input 17 D04A ...Repeated for Remote Input 18 D054 ...Repeated for Remote Input 19 D05E ...Repeated for Remote Input 20 D068 ...Repeated for Remote Input 21 D072 ...Repeated for Remote Input 22 B-42 C30 Controller System GE Multilin...
  • Page 311 ...Repeated for Remote Output 4 D230 ...Repeated for Remote Output 5 D234 ...Repeated for Remote Output 6 D238 ...Repeated for Remote Output 7 D23C ...Repeated for Remote Output 8 D240 ...Repeated for Remote Output 9 GE Multilin C30 Controller System B-43...
  • Page 312 ...Repeated for Remote Output 23 D2FC ...Repeated for Remote Output 24 D300 ...Repeated for Remote Output 25 D304 ...Repeated for Remote Output 26 D308 ...Repeated for Remote Output 27 D30C ...Repeated for Remote Output 28 B-44 C30 Controller System GE Multilin...
  • Page 313 Setting file template values (read only) ED00 FlexLogic™ displays active 0 to 1 F102 1 (Enabled) ED01 Reserved (6 items) ED07 Last settings change date 0 to 4294967295 F050 ED09 Template bitmask (750 items) 0 to 65535 F001 GE Multilin C30 Controller System B-45...
  • Page 314: B.4.2 Data Formats

    ENUMERATION: DIGITAL INPUT DEFAULT STATE 0 = Off, 1 = On, 2= Latest/Off, 3 = Latest/On F050 UR_UINT32 TIME and DATE (UNSIGNED 32 BIT INTEGER) Gives the current time in seconds elapsed since 00:00:00 January 1, 1970. B-46 C30 Controller System GE Multilin...
  • Page 315 0 = 1×72 cycles, 1 = 3×36 cycles, 2 = 7×18 cycles, 3 = 15×9 cycles F109 F118 ENUMERATION: CONTACT OUTPUT OPERATION ENUMERATION: OSCILLOGRAPHY MODE 0 = Self-reset, 1 = Latched, 2 = Disabled 0 = Automatic Overwrite, 1 = Protected GE Multilin C30 Controller System B-47...
  • Page 316 Phase Time Overcurrent 1 Negative Sequence Overvoltage Phase Time Overcurrent 2 Phase Undervoltage 1 Phase Time Overcurrent 3 Phase Undervoltage 2 Phase Time Overcurrent 4 Auxiliary Overvoltage 1 Phase Time Overcurrent 5 Phase Overvoltage 1 B-48 C30 Controller System GE Multilin...
  • Page 317 Digital Counter 6 Trip Bus 3 Digital Counter 7 Trip Bus 4 Digital Counter 8 Trip Bus 5 Digital Element 1 Trip Bus 6 Digital Element 2 RTD Input 1 Digital Element 3 RTD Input 2 GE Multilin C30 Controller System B-49...
  • Page 318 0 = Off. 1 = Pre-Fault, 2 = Fault, 3 = Post-Fault User-Programmable Pushbutton 2 User-Programmable Pushbutton 3 F131 User-Programmable Pushbutton 4 ENUMERATION: FORCED CONTACT OUTPUT STATE User-Programmable Pushbutton 5 User-Programmable Pushbutton 6 0 = Disabled, 1 = Energized, 2 = De-energized, 3 = Freeze B-50 C30 Controller System GE Multilin...
  • Page 319 A bit value of 0 = no error, 1 = error Process Bus Failure Unit Not Programmed System Exception F144 Maintenance Alert ENUMERATION: FORCED CONTACT INPUT STATE Ethernet Switch Failure 0 = Disabled, 1 = Open, 2 = Closed GE Multilin C30 Controller System B-51...
  • Page 320 4 = Group 4, 5 = Group 5, 6 = Group 6 Ethernet Port 1 Offline Ethernet Port 2 Offline F155 Ethernet Port 3 Offline ENUMERATION: REMOTE DEVICE STATE Ethernet Port 4 Offline 0 = Offline, 1 = Online Ethernet Port 5 Offline B-52 C30 Controller System GE Multilin...
  • Page 321 0 = A, 1 = B, 2 = C F166 ENUMERATION: AUXILIARY VT CONNECTION TYPE 0 = Vn, 1 = Vag, 2 = Vbg, 3 = Vcg, 4 = Vab, 5 = Vbc, 6 = Vca GE Multilin C30 Controller System B-53...
  • Page 322 0 = A, 1 = B, 2 = C, 3 = G F201 TEXT8: 8-CHARACTER ASCII PASSCODE F186 4 registers, 16 Bits: 1st Char MSB, 2nd Char. LSB ENUMERATION: MEASUREMENT MODE 0 = Phase to Ground, 1 = Phase to Phase B-54 C30 Controller System GE Multilin...
  • Page 323 0 = Unknown, 1 = Relay In Service, 2 = Relay Out Of Service MMXU2.MX.TotVAr.mag.f MMXU2.MX.TotVA.mag.f F232 MMXU2.MX.TotPF.mag.f ENUMERATION: CONFIGURABLE GOOSE DATASET ITEMS MMXU2.MX.Hz.mag.f FOR TRANSMISSION MMXU2.MX.PPV.phsAB.cVal.mag.f MMXU2.MX.PPV.phsAB.cVal.ang.f value GOOSE dataset item MMXU2.MX.PPV.phsBC.cVal.mag.f None MMXU2.MX.PPV.phsBC.cVal.ang.f GE Multilin C30 Controller System B-55...
  • Page 324 MMXU3.MX.PPV.phsBC.cVal.ang.f MMXU4.MX.A.neut.cVal.ang.f MMXU3.MX.PPV.phsCA.cVal.mag.f MMXU4.MX.W.phsA.cVal.mag.f MMXU3.MX.PPV.phsCA.cVal.ang.f MMXU4.MX.W.phsB.cVal.mag.f MMXU3.MX.PhV.phsA.cVal.mag.f MMXU4.MX.W.phsC.cVal.mag.f MMXU3.MX.PhV.phsA.cVal.ang.f MMXU4.MX.VAr.phsA.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.mag.f MMXU4.MX.VAr.phsB.cVal.mag.f MMXU3.MX.PhV.phsB.cVal.ang.f MMXU4.MX.VAr.phsC.cVal.mag.f MMXU3.MX.PhV.phsC.cVal.mag.f MMXU4.MX.VA.phsA.cVal.mag.f MMXU3.MX.PhV.phsC.cVal.ang.f MMXU4.MX.VA.phsB.cVal.mag.f MMXU3.MX.A.phsA.cVal.mag.f MMXU4.MX.VA.phsC.cVal.mag.f MMXU3.MX.A.phsA.cVal.ang.f MMXU4.MX.PF.phsA.cVal.mag.f MMXU3.MX.A.phsB.cVal.mag.f MMXU4.MX.PF.phsB.cVal.mag.f MMXU3.MX.A.phsB.cVal.ang.f MMXU4.MX.PF.phsC.cVal.mag.f MMXU3.MX.A.phsC.cVal.mag.f MMXU5.MX.TotW.mag.f MMXU3.MX.A.phsC.cVal.ang.f MMXU5.MX.TotVAr.mag.f MMXU3.MX.A.neut.cVal.mag.f MMXU5.MX.TotVA.mag.f MMXU3.MX.A.neut.cVal.ang.f MMXU5.MX.TotPF.mag.f B-56 C30 Controller System GE Multilin...
  • Page 325 MMXU6.MX.TotVAr.mag.f GGIO4.MX.AnIn18.mag.f MMXU6.MX.TotVA.mag.f GGIO4.MX.AnIn19.mag.f MMXU6.MX.TotPF.mag.f GGIO4.MX.AnIn20.mag.f MMXU6.MX.Hz.mag.f GGIO4.MX.AnIn21.mag.f MMXU6.MX.PPV.phsAB.cVal.mag.f GGIO4.MX.AnIn22.mag.f MMXU6.MX.PPV.phsAB.cVal.ang.f GGIO4.MX.AnIn23.mag.f MMXU6.MX.PPV.phsBC.cVal.mag.f GGIO4.MX.AnIn24.mag.f MMXU6.MX.PPV.phsBC.cVal.ang.f GGIO4.MX.AnIn25.mag.f MMXU6.MX.PPV.phsCA.cVal.mag.f GGIO4.MX.AnIn26.mag.f MMXU6.MX.PPV.phsCA.cVal.ang.f GGIO4.MX.AnIn27.mag.f MMXU6.MX.PhV.phsA.cVal.mag.f GGIO4.MX.AnIn28.mag.f MMXU6.MX.PhV.phsA.cVal.ang.f GGIO4.MX.AnIn29.mag.f MMXU6.MX.PhV.phsB.cVal.mag.f GGIO4.MX.AnIn30.mag.f MMXU6.MX.PhV.phsB.cVal.ang.f GGIO4.MX.AnIn31.mag.f MMXU6.MX.PhV.phsC.cVal.mag.f GGIO4.MX.AnIn32.mag.f MMXU6.MX.PhV.phsC.cVal.ang.f MMXU6.MX.A.phsA.cVal.mag.f MMXU6.MX.A.phsA.cVal.ang.f MMXU6.MX.A.phsB.cVal.mag.f GE Multilin C30 Controller System B-57...
  • Page 326 [3] CONTACT INPUTS OFF (1 to 96) November [4] VIRTUAL INPUTS (1 to 64) December [6] VIRTUAL OUTPUTS (1 to 96) [10] CONTACT OUTPUTS VOLTAGE DETECTED (1 to 64) [11] CONTACT OUTPUTS VOLTAGE OFF DETECTED (1 to 64) B-58 C30 Controller System GE Multilin...
  • Page 327 LED and bit 7 the bottom LED. A bit value of 1 indicates ENUMERATION: FLEXELEMENT™ UNITS the LED is on, 0 indicates the LED is off. 0 = Milliseconds, 1 = Seconds, 2 = Minutes GE Multilin C30 Controller System B-59...
  • Page 328 Analogs (basically all metering quantities used in protection). bitmask default variation F605 ENUMERATION: REMOTE DOUBLE-POINT STATUS INPUT Enumeration Remote double-point status input None Remote input 1 Remote input 2 Remote input 3 ↓ ↓ Remote input 64 B-60 C30 Controller System GE Multilin...
  • Page 329: C.1.1 Introduction

    The C30 relay supports IEC 61850 server services over both TCP/IP and TP4/CLNP (OSI) communication protocol stacks. The TP4/CLNP profile requires the C30 to have a network address or Network Service Access Point (NSAP) to establish a communication link. The TCP/IP profile requires the C30 to have an IP address to establish communications. These addresses are located in the menu.
  • Page 330: C.2.1 Overview

    C.2.2 GGIO1: DIGITAL STATUS VALUES The GGIO1 logical node is available in the C30 to provide access to as many 128 digital status points and associated time- stamps and quality flags. The data content must be configured before the data can be used. GGIO1 provides digital status points for access by clients.
  • Page 331: C.2.6 Mmxu: Analog Measured Values

    A limited number of measured analog values are available through the MMXU logical nodes. Each MMXU logical node provides data from a C30 current and voltage source. There is one MMXU available for each con- figurable source (programmed in the menu).
  • Page 332 The protection elements listed above contain start (pickup) and operate flags. For example, the start flag for PIOC1 is PIOC1.ST.Str.general. The operate flag for PIOC1 is PIOC1.ST.Op.general. For the C30 protection elements, these flags take their values from the pickup and operate FlexLogic™ operands for the corresponding element.
  • Page 333: C.3.1 Buffered/Unbuffered Reporting

    C.3.4 LOGICAL DEVICE NAME The logical device name is used to identify the IEC 61850 logical device that exists within the C30. This name is composed of two parts: the IED name setting and the logical device instance. The complete logical device name is the combination of settings.
  • Page 334: C.3.6 Logical Node Name Prefixes

    A built-in TCP/IP connection timeout of two minutes is employed by the C30 to detect ‘dead’ connections. If there is no data traffic on a TCP connection for greater than two minutes, the connection will be aborted by the C30. This frees up the con- nection to be used by other clients.
  • Page 335: C.4.1 Overview

    MAC address for GSSE messages. If GSSE DESTINATION MAC ADDRESS a valid multicast Ethernet MAC address is not entered (for example, 00 00 00 00 00 00), the C30 will use the source Ether- net MAC address as the destination, with the multicast bit set.
  • Page 336 The C30 has the ability of detecting if a data item in one of the GOOSE datasets is erroneously oscillating. This can be caused by events such as errors in logic programming, inputs improperly being asserted and de-asserted, or failed station components.
  • Page 337: C.4.5 Ethernet Mac Address For Gsse/Goose

    REMOTE IN 1 ITEM item to remote input 1. Remote input 1 can now be used in FlexLogic™ equations or other settings. The C30 must be rebooted (control power removed and re-applied) before these settings take effect. The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value in the sending device.
  • Page 338: C.4.6 Gsse Id And Goose Id Settings

    GSSE and GOOSE messages must have multicast destination MAC addresses. By default, the C30 is configured to use an automated multicast MAC scheme. If the C30 destination MAC address setting is not a valid multicast address (that is, the least significant bit of the first byte is not set), the address used as the destina- tion MAC will be the same as the local MAC address, but with the multicast bit set.
  • Page 339: C.5.1 Overview

    An ICD file is generated for the C30 by the EnerVista UR Setup software that describe the capabilities of the IED. The ICD file is then imported into a system configurator along with other ICD files for other IEDs (from GE or other ven- dors) for system configuration.
  • Page 340: C.5.2 Configuring Iec 61850 Settings

    Transmission GOOSE dataset may be added or deleted, or prefixes of some logical nodes may be changed. While all new configurations will be mapped to the C30 settings file when importing an SCD file, all unchanged settings will preserve the same values in the new settings file.
  • Page 341: C.5.3 About Icd Files

    Although configurable transmission GOOSE can also be created and altered by some third-party system con- figurators, we recommend configuring transmission GOOSE for GE Multilin IEDs before creating the ICD, and strictly within EnerVista UR Setup software or the front panel display (access through the Settings > Product Setup > Com- munications >...
  • Page 342 Furthermore, it defines the capabilities of an IED in terms of communication services offered and, together with its LNType, instantiated data (DO) and its default or configuration values. There should be only one IED section in an ICD since it only describes one IED. C-14 C30 Controller System GE Multilin...
  • Page 343 OptFields (seqNum) RptEnabled Other ReportControl elements DOI (name) SDI (name) DAI (name) Text Other DOI elements SDI (name) DAI (name) Text Other LN elements Other LDevice elements 842797A1.CDR Figure 0–4: ICD FILE STRUCTURE, IED NODE GE Multilin C30 Controller System C-15...
  • Page 344 BDA (name, bType, type) Other BDA elements Other BDA elements Other DAType elements Other DAType elements EnumType (id) Text EnumVal (ord) Other EnumVal elements Other EnumType elements 842798A1.CDR Figure 0–5: ICD FILE STRUCTURE, DATATYPETEMPLATES NODE C-16 C30 Controller System GE Multilin...
  • Page 345: C.5.4 Creating An Icd File With Enervista Ur Setup

    The EnerVista UR Setup will prompt to save the file. Select the file path and enter the name for the ICD file, then click OK to generate the file. The time to create an ICD file from the offline C30 settings file is typically much quicker than create an ICD file directly from the relay.
  • Page 346 Like ICD files, the Header node identifies the SCD file and its version, and specifies options for the mapping of names to signals. The Substation node describes the substation parameters: Substation PowerSystemResource EquipmentContainer Power Transformer GeneralEquipment EquipmentContainer VoltageLevel Voltage PowerSystemResource Function SubFunction GeneralEquipment 842792A1.CDR Figure 0–7: SCD FILE STRUCTURE, SUBSTATION NODE C-18 C30 Controller System GE Multilin...
  • Page 347 IdInst is the instance identification of the logical device within the IED on which the control block is located, and cbName is the name of the control block. GE Multilin C30 Controller System C-19...
  • Page 348: C.5.6 Importing An Scd File With Enervista Ur Setup

    Figure 0–9: SCD FILE STRUCTURE, IED NODE C.5.6 IMPORTING AN SCD FILE WITH ENERVISTA UR SETUP The following procedure describes how to update the C30 with the new configuration from an SCD file with the EnerVista UR Setup software. Right-click anywhere in the files panel and select the Import Contents From SCD File item.
  • Page 349 The software will open the SCD file and then prompt the user to save a UR-series settings file. Select a location and name for the URS (UR-series relay settings) file. If there is more than one GE Multilin IED defined in the SCD file, the software prompt the user to save a UR-series set- tings file for each IED.
  • Page 350: C.6.1 Acsi Basic Conformance Statement

    Setting group control REPORTING Buffered report control M7-1 sequence-number M7-2 report-time-stamp M7-3 reason-for-inclusion M7-4 data-set-name M7-5 data-reference M7-6 buffer-overflow M7-7 entryID M7-8 BufTm M7-9 IntgPd M7-10 Unbuffered report control M8-1 sequence-number M8-2 report-time-stamp M8-3 reason-for-inclusion C-22 C30 Controller System GE Multilin...
  • Page 351: C.6.3 Acsi Services Conformance Statement

    AA: TP/MC SERVER/ UR FAMILY PUBLISHER SERVER (CLAUSE 6) ServerDirectory APPLICATION ASSOCIATION (CLAUSE 7) Associate Abort Release LOGICAL DEVICE (CLAUSE 8) LogicalDeviceDirectory LOGICAL NODE (CLAUSE 9) LogicalNodeDirectory GetAllDataValues DATA (CLAUSE 10) GetDataValues SetDataValues GetDataDirectory GetDataDefinition GE Multilin C30 Controller System C-23...
  • Page 352 (qchg) S27-3 data-update (dupd) GetURCBValues SetURCBValues LOGGING (CLAUSE 14) LOG CONTROL BLOCK GetLCBValues SetLCBValues QueryLogByTime QueryLogByEntry GetLogStatusValues GENERIC SUBSTATION EVENT MODEL (GSE) (CLAUSE 14.3.5.3.4) GOOSE-CONTROL-BLOCK SendGOOSEMessage GetReference GetGOOSEElementNumber GetGoCBValues SetGoCBValues GSSE-CONTROL-BLOCK SendGSSEMessage GetReference C-24 C30 Controller System GE Multilin...
  • Page 353 (QueryLogByTime or QueryLogAfter) NOTE c8: shall declare support for at least one (SendGOOSEMessage or SendGSSEMessage) c9: shall declare support if TP association is available c10: shall declare support for at least one (SendMSVMessage or SendUSVMessage) GE Multilin C30 Controller System C-25...
  • Page 354: C.7.1 Logical Nodes Table

    R: LOGICAL NODES FOR PROTECTION RELATED FUNCTIONS RDRE: Disturbance recorder function RADR: Disturbance recorder channel analogue RBDR: Disturbance recorder channel binary RDRS: Disturbance record handling RBRF: Breaker failure RDIR: Directional element RFLO: Fault locator RPSB: Power swing detection/blocking RREC: Autoreclosing C-26 C30 Controller System GE Multilin...
  • Page 355 XSWI: Circuit switch T: LOGICAL NODES FOR INSTRUMENT TRANSFORMERS TCTR: Current transformer TVTR: Voltage transformer Y: LOGICAL NODES FOR POWER TRANSFORMERS YEFN: Earth fault neutralizer (Peterson coil) YLTC: Tap changer YPSH: Power shunt YPTR: Power transformer GE Multilin C30 Controller System C-27...
  • Page 356 ZCAP: Capacitor bank ZCON: Converter ZGEN: Generator ZGIL: Gas insulated line ZLIN: Power overhead line ZMOT: Motor ZREA: Reactor ZRRC: Rotating reactive component ZSAR: Surge arrestor ZTCF: Thyristor controlled frequency converter ZTRC: Thyristor controlled reactive component C-28 C30 Controller System GE Multilin...
  • Page 357: D.1.1 Interoperability Document

    Link Transmission Procedure: Address Field of the Link: Balanced Transmision Not Present (Balanced Transmission Only) Unbalanced Transmission One Octet Two Octets Structured Unstructured Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard GE Multilin C30 Controller System...
  • Page 358 <18> := Packed start events of protection equipment with time tag M_EP_TB_1 <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1 <20> := Packed single-point information with status change detection M_SP_NA_1 C30 Controller System GE Multilin...
  • Page 359 <103> := Clock synchronization command (see Clause 7.6 in standard) C_CS_NA_1 <104> := Test command C_TS_NA_1 <105> := Reset process command C_RP_NA_1 <106> := Delay acquisition command C_CD_NA_1 <107> := Test command with time tag CP56Time2a C_TS_TA_1 GE Multilin C30 Controller System...
  • Page 360 •Blank boxes indicate functions or ASDU not used. •‘X’ if only used in the standard direction TYPE IDENTIFICATION CAUSE OF TRANSMISSION MNEMONIC <1> M_SP_NA_1 <2> M_SP_TA_1 <3> M_DP_NA_1 <4> M_DP_TA_1 <5> M_ST_NA_1 <6> M_ST_TA_1 <7> M_BO_NA_1 <8> M_BO_TA_1 <9> M_ME_NA_1 C30 Controller System GE Multilin...
  • Page 361 M_BO_TB_1 <34> M_ME_TD_1 <35> M_ME_TE_1 <36> M_ME_TF_1 <37> M_IT_TB_1 <38> M_EP_TD_1 <39> M_EP_TE_1 <40> M_EP_TF_1 <45> C_SC_NA_1 <46> C_DC_NA_1 <47> C_RC_NA_1 <48> C_SE_NA_1 <49> C_SE_NB_1 <50> C_SE_NC_1 <51> C_BO_NA_1 <58> C_SC_TA_1 <59> C_DC_TA_1 <60> C_RC_TA_1 GE Multilin C30 Controller System...
  • Page 362 <112> P_ME_NC_1 <113> P_AC_NA_1 <120> F_FR_NA_1 <121> F_SR_NA_1 <122> F_SC_NA_1 <123> F_LS_NA_1 <124> F_AF_NA_1 <125> F_SG_NA_1 <126> F_DR_TA_1*) BASIC APPLICATION FUNCTIONS Station Initialization: Remote initialization Cyclic Data Transmission: Cyclic data transmission Read Procedure: Read procedure C30 Controller System GE Multilin...
  • Page 363 Mode A: Local freeze with spontaneous transmission Mode B: Local freeze with counter interrogation Mode C: Freeze and transmit by counter-interrogation commands Mode D: Freeze by counter-interrogation command, frozen values reported simultaneously Counter read Counter freeze without reset GE Multilin C30 Controller System...
  • Page 364 Maximum number of outstanding I-format APDUs k and latest acknowledge APDUs (w): PARAMETER DEFAULT REMARKS SELECTED VALUE VALUE 12 APDUs Maximum difference receive sequence number to send state variable 12 APDUs 8 APDUs 8 APDUs Latest acknowledge after receiving I-format APDUs C30 Controller System GE Multilin...
  • Page 365: D.1.2 Point List

    Other selection(s) from RFC 2200 (list below if selected) D.1.2 POINT LIST The IEC 60870-5-104 data points are configured through the SETTINGS PRODUCT SETUP COMMUNICATIONS DNP / menu. Refer to the Communications section of Chapter 5 for additional details. IEC104 POINT LISTS GE Multilin C30 Controller System...
  • Page 366 D.1 IEC 60870-5-104 APPENDIX D D-10 C30 Controller System GE Multilin...
  • Page 367: E.1.1 Dnp V3.00 Device Profile

    Maximum Application Fragment Size (octets): Transmitted: 292 Transmitted: configurable up to 2048 Received: Received: 2048 Maximum Data Link Re-tries: Maximum Application Layer Re-tries: None None Fixed at 3 Configurable Configurable Requires Data Link Layer Confirmation: Never Always Sometimes Configurable GE Multilin C30 Controller System...
  • Page 368 FlexLogic™. The On/Off times and Count value are ignored. “Pulse Off” and “Latch Off” operations put the appropriate Virtual Input into the “Off” state. “Trip” and “Close” operations both put the appropriate Virtual Input into the “On” state. C30 Controller System GE Multilin...
  • Page 369 No Counters Reported Configurable (attach explanation) Configurable (attach explanation) Default Object: 16 Bits (Counter 8) Default Variation: 1 32 Bits (Counters 0 to 7, 9) Point-by-point list attached Other Value: _____ Point-by-point list attached Sends Multi-Fragment Responses: GE Multilin C30 Controller System...
  • Page 370: E.1.2 Implementation Table

    Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the C30 is not restarted, but the DNP process is restarted. C30 Controller System GE Multilin...
  • Page 371 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the C30 is not restarted, but the DNP process is restarted. GE Multilin C30 Controller System...
  • Page 372 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the C30 is not restarted, but the DNP process is restarted. C30 Controller System GE Multilin...
  • Page 373 Otherwise, static object requests sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for change- event objects, qualifiers 17 or 28 are always responded.) Note 3: Cold restarts are implemented the same as warm restarts – the C30 is not restarted, but the DNP process is restarted. GE Multilin C30 Controller System...
  • Page 374: E.2.1 Binary Input Points

    Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time), Configurable Change Event Scan Rate: 8 times per power system cycle Change Event Buffer Size: 500 Default Class for All Points: 1 C30 Controller System GE Multilin...
  • Page 375: E.2.2 Binary And Control Relay Output

    Virtual Input 27 Virtual Input 59 Virtual Input 28 Virtual Input 60 Virtual Input 29 Virtual Input 61 Virtual Input 30 Virtual Input 62 Virtual Input 31 Virtual Input 63 Virtual Input 32 Virtual Input 64 GE Multilin C30 Controller System...
  • Page 376: E.2.3 Counters

    Events Since Last Clear A counter freeze command has no meaning for counters 8 and 9. C30 Digital Counter values are represented as 32-bit integers. The DNP 3.0 protocol defines counters to be unsigned integers. Care should be taken when interpreting negative counter values.
  • Page 377: E.2.4 Analog Inputs

    Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input) Change Event Variation reported when variation 0 requested: 1 (Analog Change Event without Time) Change Event Scan Rate: defaults to 500 ms Change Event Buffer Size: 256 Default Class for all Points: 2 GE Multilin C30 Controller System E-11...
  • Page 378 E.2 DNP POINT LISTS APPENDIX E E-12 C30 Controller System GE Multilin...
  • Page 379: F.1.1 Revision History

    5.4x 26 June 2007 URX-242 1601-0088-R2 5.4x 31 August 2007 URX-246 1601-0088-R3 5.4x 17 October 2007 URX-251 1601-0088-S1 5.5x 7 December 2007 URX-253 1601-0088-S2 5.5x 22 February 2008 URX-258 1601-0088-S3 5.5x 12 March 2008 URX-260 GE Multilin C30 Controller System...
  • Page 380: F.1.2 Changes To The C30 Manual

    RELEASE DATE 1601-0088-T1 5.6x 27 June 2008 08-0390 1601-0088-T2 5.6x 02 November 2009 09-1279 F.1.2 CHANGES TO THE C30 MANUAL Table F–2: MAJOR UPDATES FOR C30 MANUAL REVISION T2 PAGE PAGE CHANGE DESCRIPTION (T1) (T2) Title Title Update Manual part number to 1601-0088-T2...
  • Page 381 APPENDIX F F.1 CHANGE NOTES Table F–4: MAJOR UPDATES FOR C30 MANUAL REVISION S3 PAGE PAGE CHANGE DESCRIPTION (S2) (S3) Title Title Update Manual part number to 1601-0088-S3 Update Updated COMMUNICATIONS specifications section 2-10 2-11 Update Updated INTER-RELAY COMMUNICATIONS specifications section...
  • Page 382 F.1 CHANGE NOTES APPENDIX F Table F–8: MAJOR UPDATES FOR C30 MANUAL REVISION R2 PAGE PAGE CHANGE DESCRIPTION (R1) (R2) Title Title Update Manual part number to 1601-0088-R2 Table F–9: MAJOR UPDATES FOR C30 MANUAL REVISION R1 PAGE PAGE CHANGE...
  • Page 383: F.2.1 Standard Abbreviations

    MTR ....Motor FD ....Fault Detector MVA ....MegaVolt-Ampere (total 3-phase) FDH....Fault Detector high-set MVA_A....MegaVolt-Ampere (phase A) FDL ....Fault Detector low-set MVA_B....MegaVolt-Ampere (phase B) FLA....Full Load Current MVA_C....MegaVolt-Ampere (phase C) FO ....Fiber Optic GE Multilin C30 Controller System...
  • Page 384 RST ....Reset RSTR ..... Restrained RTD ....Resistance Temperature Detector X ....Reactance RTU ....Remote Terminal Unit XDUCER..Transducer RX (Rx) ..Receive, Receiver XFMR..... Transformer s ..... second Z..... Impedance, Zone S..... Sensitive C30 Controller System GE Multilin...
  • Page 385: F.3.1 Ge Multilin Warranty

    24 months from date of shipment from factory. In the event of a failure covered by warranty, GE Multilin will undertake to repair or replace the relay providing the warrantor determined that it is defective and it is returned with all transportation charges prepaid to an authorized service centre or the factory.
  • Page 386 F.3 WARRANTY APPENDIX F C30 Controller System GE Multilin...
  • Page 387 Modbus registers ............B-39 C37.94SM COMMUNICATIONS ........3-38 settings ................. 5-40 CE APPROVALS .............. 2-15 specifications ..............2-8 CHANGES TO C30 MANUAL ..........F-2 COUNTERS CHANGES TO MANUAL ..........F-3, F-4 actual values ..............6-6 CHANNEL COMMUNICATION .......... 3-29 settings ................. 5-93 CHANNEL TESTS ..............
  • Page 388 Modbus registers ............B-11 DISCONNECT SWITCH specifications ..............2-9 FlexLogic™ operands ............ 5-70 via EnerVista software ............. 4-2 logic ................5-66 EVENTS SETTING ............5-3 Modbus registers ............B-20 EXCEPTION RESPONSES ..........B-5 settings ................. 5-64 C30 Controller System GE Multilin...
  • Page 389 ............3-13, 3-15, 3-19 specifications ............2-9, 2-11 specifications ..............2-10 ISO-9000 REGISTRATION ..........2-15 FORM-C RELAY outputs ..............3-13, 3-19 specifications ..............2-10 FUNCTION SETTING ............5-3 FUSE ................2-10 KEYPAD ..............1-17, 4-22 GE Multilin C30 Controller System...
  • Page 390 I/O ............... 3-21 low range ...............2-10 withdrawal ..............3-6, 3-7 specifications ..............2-10 MOUNTING ..............3-1, 3-2 PREFERENCES Modbus registers ............B-13 PROCESS BUS overview ................3-13 PRODUCT INFORMATION ........6-13, B-8 PRODUCT SETUP ............. 5-4 NAMEPLATE ..............1-1 C30 Controller System GE Multilin...
  • Page 391 ................5-112 specifications ..............2-9 Modbus registers ..........B-25, B-26 overview ..............5-111 settings ............ 5-57, 5-111, 5-112 specifications ..............2-10 TERMINALS ............... 3-8 TESTING SALES OFFICE ..............1-1 force contact inputs ............5-120 GE Multilin C30 Controller System...
  • Page 392 ENERVISTA UR SETUP USER-DEFINABLE DISPLAYS example ................ 5-49 invoking and scrolling ............ 5-47 Modbus registers ..........B-13, B-17 WARRANTY ..............F-7 settings ..............5-47, 5-49 WEB SERVER PROTOCOL ..........5-27 specifications ..............2-8 WEBSITE ................1-1 USER-PROGRAMMABLE LEDs C30 Controller System GE Multilin...

Table of Contents