Appendix B Relay Contact Ratings - GE VersaMax Manual

Table of Contents

Advertisement

Relay Contact Ratings
Appendix
B
Mechanical Rating
Relay contacts are rated for 10
Electrical Rating
The relay contact use in VersaMax modules meet Underwriters Laboratories' Pilot Duty
Rating for Control Circuits. Contact life depends on type of load and current, as
summarized in the table below.
Operating
Voltage
24 to 125VAC
24 to 125VAC
24 to 125VAC
24 to 125VAC
250VAC
250VAC
250VAC
250VAC
5 to 31VDC
5 to 31VDC
5 to 31VDC
5 to 31VDC
32 to 125VDC
Power Factor = 0.4 minimum for AC inductive loads
Time Constant – 7mS for DC inductive loads
Installing suitable suppression across inductive loads enhances reliability. For DC, a free-
wheeling diode provides suitable suppression. For AC, an R-C filter can be used.
GFK-1504K
7
operations.
Maximum Current for Load Type
Resistive
Inductive *
2.0 Amp
0.35 Amp
1.00 Amp
1.5 Amp
0.20 Amp
0.8 Amp
0.10 Amp
2.0 Amp
0.15 Amp
1.00 Amp
1.0 Amp
0.6 Amp
2.0 Amp
0.70 Amp
2.00 Amp
1.1 Amp
0.25 Amp
0.7 Amp
0.10 Amp
0.2 Amp
not rated
Typical Contact
Life (operations)
300,000
100,000
500,000
1,000,000
180,000
30,000
500,000
1,000,000
200,000
50,000
500,000
1,000,000
300,000
B-1