IC200MDL243
Input Module, 120VAC Isolated 16 Points
Module Specifications
Module Characteristics
Points
Module ID
Isolation:
User input to logic (optical)
and frame ground
Group to group
Point to point
LED indicators
Backplane current
consumption
External power supply
Thermal derating
Input Characteristics
Input voltage
On state voltage
Off state voltage
On state current
Off state current
On response time
Off response time
Input impedance
7-22
VersaMax® Modules, Power Supplies, and Carriers User's Manual – March 2003
16 Isolated Inputs
88048804
250VAC continuous; 1500VAC for 1 minute
Not applicable
250VAC continuous; 1500VAC for 1 minute
One LED per point shows individual point ON/OFF status
OK LED indicates backplane power is present
5V output: 100mA maximum
None
See diagram
0 to 132VAC (47 to 63Hz), 120VAC nominal
70 to 132VAC
0 to 20VAC
5mA minimum
2.5mA maximum
1 cycle maximum
2 cycles maximum
8.6kOhms (reactive) at 60Hz, typical
10.32kOhms (reactive) at 50Hz, typical