Mixed Module, 24Vdc Positive Logic Input 20 Points; Output Relay 2.0 Amp 12 Points - GE VersaMax Manual

Table of Contents

Advertisement

9
IC200MDD840

Mixed Module, 24VDC Positive Logic Input 20 Points /

Output Relay 2.0 Amp 12 Points

Discrete input/output module IC200MDD840 provides 20 discrete inputs and 12 relay
outputs. The inputs form two groups of 10 points. Inputs are positive logic or sourcing-type
inputs; they receive current from devices and return the current on the common. The relay
outputs form two groups of 6 points. Each output group can drive a maximum of 8 Amps.
Power for module operation comes from the backplane. Output loads must be powered by
an external source.
Intelligent processing for the module is performed by the CPU or NIU. The module
provides 20 bits of discrete input data and receives 12 bits of discrete output data.
LED Indicators
Individual green LEDs indicate the on/off state of the output points and input points.
The output LEDs are logic-driven and independent of the load conditions.
The green OK LED is on when backplane power is present to the module.
Configuration Parameters
The module's basic input on/off response time is 0.5ms.
For some applications, it may be preferable to add additional filtering to compensate for
conditions such as noise spikes or switch bounce. Input filter times of 0ms, 1.0ms, or 7.0ms
are selectable via software configuration, for total response times of 0.5ms, 1.5ms, and 7.5ms
respectively. The default is 1.0ms filter time (total response time is 1.5ms).
9-2
VersaMax® Modules, Power Supplies, and Carriers User's Manual – March 2003
I/Q
1
2
3
4
5
6
7
8
9
10
IND CONT EQ FOR HAZ LOC
CLASS I DIV 2 GROUPS ABCD
Temp Code T4 Ambient 60C
CLASS I ZONE 2 GROUP IIC
Ex nA IIC OC ≤ Ta ≤ 60C
Ex nV II Demko No 98Y. 125014
11 12 13 14 15 16 17 18 19 20
I/Q
OK
1
2
3
4
5
6
IC200MDD840
IN
24VDC
20PT
OUT
RLY
2A
12PT
1234567
831
7
8
9 10 11 12
OK
GFK-1504K