8
IC200MDL741
Output Module, 24VDC Positive Logic 0.5 Amp, w/ESCP 16 Points
Module Specifications
Module Characteristics
Points
Module ID
Isolation:
User input to logic (optical)
and to frame ground
Group to group
Point to point
LED indicators
Backplane current consumption
External power supply
Thermal derating
Output Characteristics
Output voltage
Output voltage drop
Load current
Steady-state overcurrent trip
point
Output leakage current
On response time
Off response time
Protection (each output)
External Power Supply Requirements
The external power supply used to power the loads must provide sufficient field
power for the module during short circuit events. When a load is shorted, an
inadequate external power supply may allow field power to drop below the specified
operating range, causing misoperation of the module. The external power supply
must be capable of providing short circuit energy without degradation of output
voltage levels. The amount of energy required depends on the number of
simultaneously-shorted points that might occur. Refer to power supply short circuit
operation specifications when selecting the power supply to be used with the loads.
Local energy storage (either batteries or capacitors) can be used to compensate for
insufficient power supply characteristics. Additional best practices including
minimizing wiring resistance from the external power supply to the module must be
observed.
8-22
VersaMax® Modules, Power Supplies, and Carriers User's Manual – March 2003
1 group of 16 outputs
FFFF8080
250VAC continuous; 1500VAC for 1 minute
Not applicable
None
One green LED per point shows individual point on/off state
One amber LED per point shows individual point overloads
FLD PWR LED indicates field power is present
OK LED indicates backplane power is present
5V output: 75mA maximum
+18 to +30VDC, +24VDC nominal
See diagrams
+18 to +30VDC, +24VDC nominal
0.5V maximum
0.5A at 30VDC maximum (resistive)
2.0A inrush maximum for 100ms
1.6A typ., 0.7A to 2.5A max range
0.5mA at 30VDC maximum
0.5ms, maximum
0.5ms, maximum
Short circuit protection, overcurrent protection, free-wheeling