Specifications
Input Voltage
Input Power
Holdup Time
Inrush Current
Output Voltage
Protection
Output Current
Total
3.3VDC Output
5VDC Output
The total output current should not exceed 1.5A. For example, if 3.3V @ 1.0A is required,
0.5A is available on the 5V output.
Wiring
DC- must be grounded to frame / earth ground. DC- is grounded to frame internally in the
Power Supply. As a result, floating power supplies cannot be used.
GFK-1504K
Chapter 3 Power Supplies
12VDC Expanded 3.3 V Power Supply
9.6 to 15VDC, 12VDC nominal
11W
10ms
25A at 12VDC
30A at 15VDC
5VDC, 3.3VDC
Short circuit, overload, reverse polarity
1.5A maximum
1.0A maximum
(1.5A - I
) maximum
3.3V
DC+
DC-
3
IC200PWR202
3-13