Designing the Control Cabinet

Arranging the Components in the Control Cabinet

High temperature
Risk of damage to temperature-sensitive control
cabinet components in the area of the cooling air
outlet.
CAUTION
Make sure the distances are sufficient.
Control Cabinet with Multiple Line Structure
Note:
In particular when arranging components in multiple lines
within the control cabinet, it is important to observe their max.
air inlet temperature (see technical data) and, if necessary, to
mount air baffles with blowers used for this specific purpose.
Discharge direction of the
warmed air in the flow-off area
Inlet area of the cooling air for
Discharge direction of the
Additional
warmed air in the flow-off area
blower
Inlet area of the cooling air for
Fig. 7-2: Example of arrangement for multiple line structure
Rexroth EcoDrive Cs Drives
the upper device line
the lower device line
DOK-ECODR3-DKC**.3-CS*-PR02-EN-P
Exhaust air
to the air
conditioner
For example:
air baffle
Supply air
from the air
conditioner