Computing Phase Current On The Mains - REXROTH EcoDrive Cs Project Planning Manual

Table of Contents

Advertisement

Rexroth EcoDrive Cs Drives

Computing Phase Current on the Mains

DOK-ECODR3-DKC**.3-CS*-PR02-EN-P
To select a suitable mains contactor and fuses for the power connections
it is necessary to first compute the phase current I
The mains-side phase current I
connecting power S
.
N1
Selecting the mains connecting power in the list or compute it according
to the following formula. With multiple controllers, add the individual
powers.
The mains connecting power can be determined
by selecting the mains connecting power in the list resp. the technical
data
- or -
by computing it according to the following formula.
Note :
With multiple controllers, add the individual powers and, if
necessary, take a coincidence factor into account, because
often not all servo axes require full power simultaneously.
P
ZWD
P
:
required DC bus continuous power in W
ZWD
M
:
rms torque in Nm
EFF
n
:
mean speed in min-1
MITTEL
k:
factor for motor and controller efficiency
Fig. 6-13: Computing DC bus power
S
:
connected load in VA
N1
P
:
DC bus continuous power in W
ZWD
F:
connected load factor due to the non-sinusoidal phase current
Fig. 6-14: Computing mains connected load
Single-phase load:
Three-phase load:
I
:
mains-side phase current in A
N1
S
:
connected load in VA
N1
U
:
voltage between phases of the mains in V
N1
Fig. 6-15: Computing mains-side phase current
Mains and Supply Voltage Connection
at the mains.
N
is determined out of the mains
N1
π
M
n
2
EFF
MITTEL
k ⋅
=
60
S
=
P
F
N1
ZWD
I
=
N1
I
=
N1
U
N1
6-11
S
N1
U
N1
S
N1
3